Electrical Application Details for App #: B375827
Premises: 147 VANDERBILT AVENUE BROOKLYN BIN: 3054245     Block: 1887   Lot: 3
   
Application Completed and Certified

Filed: 147 VANDERBILT AV Census Tract:   187 Health Area:  1200
CELLAR THRU 3 FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11205 Community Board:   302
DOB Cross Street(s):   PARK AVENUE,    MYRTLE AVENUE
Status:   C - JOB IS SIGNED OFF 09/05/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/18/2013 1:10 PM
Application Entered:   12/18/2013 Job Start Date:   12/19/2013
Last Change:   09/05/2014 Job End Date:   10/15/2014
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     08/29/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011891 Licensee Name: STEVEN OLKHOVETSKY
Firm: 003525 Firm Name: GREY GOOSE ELECTRIC CORP
Firm Phone: 646-369-3525  Firm Address: 2063 ATLANTIC AVENUE BROOKLYN NY 11233 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $299.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LIOR RAVIV
Owner Business Name: VANDERBILT APTS. LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    12           
001    28  25    12  28             
002    28  25    12  28         
003    28  25    12  28         
Buildings Total 92  87    41  92              
Total Units : 321 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 4 - Removed Meters 3 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/18/2013 Notice: 1 - FIRST NOTICE 08/07/2014
Power Issued: 12/18/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B375827
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2014 08/07/2014 CCH A E (60) (2) Y
INSPECTION COMMENTS: N
 
(2) 08/29/2014 09/02/2014 CJE C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B375827
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
#14 WIRE GREEN USE FOR GROUNDING ALL OUTLETS
RSLV 08/04/2014 08/04/2014 08/29/2014
 
002 (999) OTHER
CIR NOT GROUP 300.20
RSLV 08/04/2014 08/04/2014 08/29/2014