BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B375763
Premises: 23 CATON PLACE BROOKLYN BIN: 3124033     Block: 5320   Lot: 24
   
Application Completed and Certified

Filed: 23 CATON PL Census Tract:   504
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11218 Community Board:   307
Related Job Number:    301880891
DOB Cross Street(s):   OCEAN PARKWAY,    EAST 8 STREET
Status:   C - JOB IS SIGNED OFF 05/27/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/17/2013 Job Start Date:   11/11/2013
Last Change:   05/27/2015 Job End Date:   10/31/2014
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     03/25/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011915 Licensee Name: MIKHAIL MIKHAYLOV
Firm: 003550 Firm Name: APS ELECTRIC INC
Firm Phone: 718-996-9187  Firm Address: 36-36 33RD STREET, SUITE 205 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $3,598.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   D1-ELEVATOR APT
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52031     Submittal #: 13A0491  
Owner / Occup: MOSHE FELLER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  6  5-800AMP; 1-1200AMP
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  8  #1
C. Over 1/0 to 250 MCM  3  250MCM
D. Over 250 MCM  14  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  8  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 126 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 127 - Removed Meters 0 = Total Meters 127

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/17/2013 Notice: 1 - FIRST NOTICE 03/16/2015
Power Issued: 12/17/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B375763
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/24/2015 03/04/2015 PAT V E (240) (5) Y
INSPECTION COMMENTS: JOCKEY PUMP FEEDERS, BONDING NOT 12 1/2% PLEASE CHECK 5- 800 AMPS SER SW COPPER BASS
 
(2) 03/11/2015 03/16/2015 CJH A R E (70) (1) Y
INSPECTION COMMENTS: FIRE PUMP LABEL NOT RECONIZABLE
 
(3) 03/25/2015 04/01/2015 PAT C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B375763
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANIC BAR FOE ELEC RM NOT PROVIDED 110.26
RSLV 02/24/2015 02/24/2015 03/11/2015
 
002 (108) FIRE PUMPS DISCONNECT MEANS/OVERCURRENT PROTECTION NOT 600% FULL
FIRE PUMP OVERCURRENT PROTECTION 695.4
RSLV 02/24/2015 02/24/2015 03/11/2015
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
JOCKEY PUMP D SWITCH 110.2B
RSLV 02/24/2015 02/24/2015 03/11/2015
 
004 (999) OTHER
UNDERSIZED BONDING JUMPER FO RSER/SWS 250.28
RSLV 02/24/2015 02/24/2015 03/11/2015
 
005 (228) USING PANEL AS A RACEWAY
1200AMPS SERVICES IS BEING USED AS A RACEWAY 312.8
RSLV 02/24/2015 02/24/2015 03/11/2015
 
006 (999) OTHER
CELLAR SVC AREA COMMUNICATION BAR NOT INSTALLED 250.94
RSLV 03/11/2015 03/11/2015 03/25/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back