BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B375645
Premises: 151 CONOVER STREET BROOKLYN BIN: 3008580     Block: 565   Lot: 1
   

DOB NOW: Inspections


Filed: 165 CONOVER ST Census Tract:   53
GND Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
DOB Cross Street(s):   SULLIVAN STREET,    WOLCOTT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   12/13/2013 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:    Complaint Number:    3464459
Last Inspection By:   COHN, MARTIN       On     12/12/2013      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: NEW START GROUP INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/13/2013
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 12/13/2013
Contractor's Comments:  ELEVATOR MACHINE ROOM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B375645
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/12/2013 12/13/2013 MC2 W (60) (4)
INSPECTION COMMENTS: SEE VIOLATION DETAILS

OBJECTION FOR APPLICATION #: B375645
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
WORK WITHOUT PERMIT ELECTRICAL WIRING OF TWO PASSENGER ELEV. FEEDERSRACEWAY DISCONNECT SWITCH, CONTROL PANELS, BRANCH CIRCUITS. 27.3018B
OPEN 12/12/2013 12/12/2013
 
002 (999) OTHER
CAB LIGHTS DISCONNECT SWITCHES, NOT LOCATED IN MACHINE ROOM. 620.53
OPEN 12/12/2013 12/12/2013
 
003 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ELEVATOR DISCONNECT SWITCHES FOR 3P8562 AND 3P8563 HAS NEUTRALBONDED AFTER SERVICE SWITCH. 250.24A5
OPEN 12/12/2013 12/12/2013
 
004 (999) OTHER
FAILURE TO PROPERLY CONNECT GROUNDING CONDUCTORS TO LUG CONNECTIONSDOUBLE LUGGED. 110.14A. NOT FINAL INSPECTION. REF. #3464459
OPEN 12/12/2013 12/12/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order