BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B374752
Premises: 1799 BEDFORD AVENUE BROOKLYN BIN: 3035252     Block: 1328   Lot: 6
   
Application Completed and Certified

Filed: 1799 BEDFORD AV Census Tract:   800 Health Area:  5400
BASEMENT 1,2,3,4,FL Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
DOB Cross Street(s):   LEFFERTS AVENUE,    LINCOLN ROAD
Status:   C - JOB IS SIGNED OFF 10/24/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2013 10:04 AM
Application Entered:   11/15/2013 Job Start Date:   11/18/2013
Last Change:   10/24/2014 Job End Date:   10/17/2014
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     10/06/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011063 Licensee Name: MELVIN A BRANDL
Firm: 000219 Firm Name: BRANDL ELECTRIC INC.
Firm Phone: 718-327-5677  Firm Address: 71-34 MAIN STREET FLUSHING NY 11367 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $798.75
Other Work:   ADEQUATE WIRING
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID SPUTZ
Owner Business Name: CROWN REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600AMP 3 PH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  2 SET 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  27  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    12               
002    14               
003    14               
004    14               
Buildings Total 27  54  27    27                
Total Units : 135 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 27 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/15/2013 Notice: 1 - FIRST NOTICE 07/24/2014
Power Issued: 11/15/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B374752
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2014 04/28/2014 PAT N (0) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 06/03/2014 06/09/2014 CJE V G (95) (6) Y
INSPECTION COMMENTS: NO ACCESS TO APT ON 2ND FL (D,F,A+B) 3FL (B,D,E+G) 4FL (A,B,E,F,G) 1FL (A+C)
 
(3) 07/22/2014 07/24/2014 CJH V R E (45) (3) Y
INSPECTION COMMENTS: FOLLOWING APT WAS INSPECTION 1D, 1G, 2G, 3G, & 4D
 
(4) 09/11/2014 09/15/2014 CJH J R G (75) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APT 1C 2A BC 3G 4B CDEF
 
(5) 09/25/2014 09/29/2014 JSB N (30) (0) Y
INSPECTION COMMENTS: N
 
(6) 10/06/2014 10/15/2014 PAT C G (70) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B374752
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
"B" LINE NEW BRANCH CIRCUIT FOR SMOKE DETECTOR NO AFCI PROTECTION210.12(B)
RSLV 06/03/2014 06/03/2014 07/22/2014
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
APT ON THE "C" LINE NEW BRANCH CIRCUIT FOR SMOKE DETECTOR. NO AFCIPROTECTION ART. 210.12(B)
RSLV 06/03/2014 06/03/2014 07/22/2014
 
003 (999) OTHER
A/C RECEPTACLE INSTALLED NOT FLUSHED WITH WALL. ART 314.20
RSLV 06/03/2014 06/03/2014 07/22/2014
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
"D" APT NO AFCI FOR SMOKE DETECTOR. ART 210.12(B)
RSLV 06/03/2014 06/03/2014 07/22/2014
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
"A" APT NO AFCI FOR SMOKE DETECTOR. ART 210.12(B)
RSLV 06/03/2014 06/03/2014 07/22/2014
 
006 (999) OTHER
MULTIWIRE CIRCUITS IN PLP. MEANS OF DISCONNECT NOT SIMULTANEOUS ART210.4(B)
RSLV 06/03/2014 06/03/2014 07/22/2014
 
007 (999) OTHER
ALL APTS THROUGHOUT A.C RECEPTACLE NOT TR 406-11
RSLV 07/22/2014 07/22/2014 09/11/2014
 
008 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
THROUGHOUT ALL APTS 20A BRAKERS ON #14 CONDUCTOR 240.3
RSLV 07/22/2014 07/22/2014 09/11/2014
 
009 (999) OTHER
BSMT SVC ENT CONDUCTOR WHT USED AS HOT 200.7
RSLV 07/22/2014 07/22/2014 09/11/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.