| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
600AMP 3 PH |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
2 SET 350 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
27 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED "B" LINE NEW BRANCH CIRCUIT FOR SMOKE DETECTOR NO AFCI PROTECTION210.12(B) |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED APT ON THE "C" LINE NEW BRANCH CIRCUIT FOR SMOKE DETECTOR. NO AFCIPROTECTION ART. 210.12(B) |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 003 |
(999) |
OTHER A/C RECEPTACLE INSTALLED NOT FLUSHED WITH WALL. ART 314.20 |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED "D" APT NO AFCI FOR SMOKE DETECTOR. ART 210.12(B) |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED "A" APT NO AFCI FOR SMOKE DETECTOR. ART 210.12(B) |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 006 |
(999) |
OTHER MULTIWIRE CIRCUITS IN PLP. MEANS OF DISCONNECT NOT SIMULTANEOUS ART210.4(B) |
RSLV |
06/03/2014 |
06/03/2014 |
07/22/2014 |
| |
| 007 |
(999) |
OTHER ALL APTS THROUGHOUT A.C RECEPTACLE NOT TR 406-11 |
RSLV |
07/22/2014 |
07/22/2014 |
09/11/2014 |
| |
| 008 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE THROUGHOUT ALL APTS 20A BRAKERS ON #14 CONDUCTOR 240.3 |
RSLV |
07/22/2014 |
07/22/2014 |
09/11/2014 |
| |
| 009 |
(999) |
OTHER BSMT SVC ENT CONDUCTOR WHT USED AS HOT 200.7 |
RSLV |
07/22/2014 |
07/22/2014 |
09/11/2014 |