| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
4 |
4-60A,1- 226V |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
#6 AWG |
| B. Over #2 to 1/0 |
1 |
#110 AWG |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(340) |
RECEPTACLES NOT TAMPERPROOF (ALL FLOORS) ALL THROUGHOUT |
RSLV |
10/04/2017 |
10/04/2017 |
11/27/2017 |
| |
| 002 |
(134) |
GROUNDING CONNECTION IS NOT WITHIN 5FT (BASEMENT) FOR SERVICE EQUIPMENT |
RSLV |
10/04/2017 |
10/04/2017 |
11/27/2017 |
| |
| 003 |
(999) |
OTHER (OPEN SPACE) ALL OUTDOOR GFCI NOT WR/TR LISTED ART 406.8 |
RSLV |
10/04/2017 |
10/04/2017 |
11/27/2017 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 001)001 FL BATH LUMINAIRE CABLES NOT PROPERLY TERMINATED 320.40 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 005 |
(999) |
OTHER (FLOOR: 001) 001 FL BATH ROOM LUMINAIRE NOT GROUNDED PROPERLY 410.46 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 006 |
(999) |
OTHER (FLOOR: 001)001 FL KITCHEN COUNTER TOP RECEPT OUTLETS ZIP SCREWS IN USED 250.8 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 007 |
(282) |
MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS (FLOOR: 002) 002,003 FL KITCHEN COUNTER TOP 1 CKT PROVIDED 210.52 B1 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 008 |
(999) |
OTHER (FLOOR: 002)002,003 FL SMOKE, LIVING ROOM NOT AFIC PROTECTED 210.12 B |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 009 |
(999) |
OTHER (FLOOR: 002) 002 FL PNL CKT BREAKER DEFECTIVE 110.2 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS) THROUGHOUT PNL CKT NOT GROUPED 210.4 D |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)THROUGHOUT LIVING, BED ROOM WALL SWITCHES NOT ACCESSIBLE 110.2 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 012 |
(999) |
OTHER (BASEMENT) BSMT PNL MULTI CKT ON SAME PHASE 210.7 B |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 013 |
(999) |
OTHER (BASEMENT) BSMT AC CKT NOT PROVIDED 210.52 (I) |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |
| |
| 014 |
(999) |
OTHER (BASEMENT) BSMT LAUNDRY CKT NOT PROVIDED 210.11 C2 |
RSLV |
11/27/2017 |
11/27/2017 |
12/16/2017 |