BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B373092
Premises: 1269 EAST 18 STREET BROOKLYN BIN: 3180707     Block: 6738   Lot: 40
   
Application Completed and Certified

Filed: 1269 E 18 ST Census Tract:   538 Health Area:  7310
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
DOB Cross Street(s):   AVENUE L,    BAY AVENUE
Status:   C - JOB IS SIGNED OFF 03/19/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/03/2013 10:36 AM
Application Entered:   10/03/2013 Job Start Date:   10/05/2013
Last Change:   03/19/2015 Job End Date:   10/07/2013
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     03/10/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010968 Licensee Name: FRANCIS CAPORALE
Firm: 002308 Firm Name: BLAZE ELECTRIC INC.
Firm Phone: 718-369-0810  Firm Address: 681 5TH AVENUE BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
9 - OTHER
Total Fee:  $103.00
Other Work:   BULLETIN #8
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MORRIS LIEBERMAN
Owner Business Name: LILMOR MANAGEMENT
Authorized Representative:  MORRIS LIEBERMAN
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS             
Buildings Total               
Total Units : 14 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/19/2015 Notice: 1 - FIRST NOTICE 07/29/2014
Power Issued: 03/19/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B373092
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2014 07/29/2014 CJE A (40) (6) Y
INSPECTION COMMENTS: N
 
(2) 03/10/2015 03/19/2015 DAH C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B373092
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASE - NEUTRALS NOT TERMINATED TO BAR IN PANEL ART. 408.41
RSLV 07/23/2014 07/23/2014 03/10/2015
 
002 (999) OTHER
BASE - FIXTURES NOT GROUNDED. ART 410.46
RSLV 07/23/2014 07/23/2014 03/10/2015
 
003 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
GFCI - RECEPTACLES NOT INSTALLED NEAR BOILER UNIT 210.63
RSLV 07/23/2014 07/23/2014 03/10/2015
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASE - NO GROUND INSTALLED TO CONTROLLER ART ART. 250.112
RSLV 07/23/2014 07/23/2014 03/10/2015
 
005 (999) OTHER
BASE - MULTIWIRE CIRCUITS MEANS OF DISCONNECT NOT SIMULTANEOUS ART210.4(B)
RSLV 07/23/2014 07/23/2014 03/10/2015
 
006 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
BASE - NEUTRAL NOT GROUPED WITH CIRCUIT CONDUCTORS ART 300.3(B)
RSLV 07/23/2014 07/23/2014 03/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.