BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B371420
Premises: 110 ROCHESTER AVENUE BROOKLYN BIN: 3396730     Block: 1349   Lot: 33
   
Application Completed and Certified

Filed: 110 ROCHESTER AV Census Tract:   307
ELEVATOR Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11233 Community Board:   308
Related Job Number:    320328329
DOB Cross Street(s):   DEAN STREET,    BERGEN STREET
Status:   C - JOB IS SIGNED OFF 06/30/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/17/2013 Job Start Date:   12/16/2013
Last Change:   06/30/2014 Job End Date:   02/03/2014
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     06/26/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010036 Licensee Name: GERALD A OTTEN
Firm: 001107 Firm Name: DOBS ELEVATOR COMPANY
Firm Phone: 917-339-9600  Firm Address: 1 PENN PLAZ 250 W. 34TH STREET STE410 NEW YORK NY 10119 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH PROCIDA
Owner Business Name: PLK DEVELOPMENT
Authorized Representative:  GERALD OTTEN
Relationship To Owner:    AUTHORIZED REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/30/2014 Notice: 1 - FIRST NOTICE 02/05/2014
Power Issued: 06/30/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FURNISH AND INSTALL ONE(1)NEW HYDRAULIC ELEVATOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B371420
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2014 02/05/2014 CJH A (30) (7) Y
INSPECTION COMMENTS: N
 
(2) 06/26/2014 06/30/2014 CCH C R E (50) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B371420
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ALL DIS SWITCHES 250.24 (A5)
RSLV 01/28/2014 01/28/2014 06/26/2014
 
002 (999) OTHER
MACHINE RM DIS SW KO MISSING 110.12 (A)
RSLV 01/28/2014 01/28/2014 06/26/2014
 
003 (999) OTHER
PIT LIGHTS RECEPTICLES OUTLETS SAME CIR 624.24
RSLV 01/28/2014 01/28/2014 06/26/2014
 
004 (999) OTHER
CAR LIGHTS RECEPTICLE OUTLET SAME CIR 624.22
RSLV 01/28/2014 01/28/2014 06/26/2014
 
005 (999) OTHER
CAR TOP GFCI OPEN GND 110.2A
RSLV 01/28/2014 01/28/2014 06/26/2014
 
006 (999) OTHER
MACHINE ROOM GFCI LIGHTS SAME CIR 620.23
RSLV 01/28/2014 01/28/2014 06/26/2014
 
007 (999) OTHER
MACHINE RM ELEVATOR CONTROLLER EQUIPTMENT NOT LISTED 110.3
RSLV 01/28/2014 01/28/2014 06/26/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order