BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B371231
Premises: 140 SMITH STREET BROOKLYN BIN: 3001226     Block: 193   Lot: 26
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 140 SMITH ST Census Tract:   43 Health Area:  2400
SMITH STREET Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   DEAN STREET,    BERGEN STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/12/2013 5:12 PM
Application Entered:   08/12/2013 Job Start Date:   08/12/2013
Last Change:   08/22/2025 Job End Date:   09/30/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     02/25/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010813 Licensee Name: RICHARD ESPOSITO
Firm: 002078 Firm Name: ALL WAYS ELECTRIC CORP.W
Firm Phone: 800-924-9297  Firm Address: 112 WEST 34TH STREET FLR 17 NEWYORK NY 10120 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $236.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: INTERMIX
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMP MAIN BREAKER
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12    12             
001    30  12    30             
ROF                   
Buildings Total 42  19    42              
Total Units : 117 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/03/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B371231
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/03/2014 09/09/2014 FWE N (20) (0) Y
INSPECTION COMMENTS: NO SHOW TENANT
 
(2) 02/25/2015 03/03/2015 CLC V (45) (5) Y
INSPECTION COMMENTS: NO ACCESS TO AC UNIT OR LED TRANSFORMERS

OBJECTION FOR APPLICATION #: B371231
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
SVC SW 3/0 WIRE FUSED AT 225AMPS
OPEN 02/25/2015 02/25/2015
 
002 (999) OTHER
SVC SW BONDING UNDER SIZE 250.102 C METER
OPEN 02/25/2015 02/25/2015
 
003 (999) OTHER
SVC SW NEUTRAL NOT BONDED 250.24 B
OPEN 02/25/2015 02/25/2015
 
004 (999) OTHER
SUBPANEL NEUTRAL BONDED AFTER SVC SW 250.24A5
OPEN 02/25/2015 02/25/2015
 
005 (999) OTHER
SVC BRANCH CKTS NEUTRALS NOT ON NEUTRAL BAR 408.40
OPEN 02/25/2015 02/25/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back