BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B370284
Premises: 386 VAN BRUNT STREET BROOKLYN BIN: 3008609     Block: 575   Lot: 28
   
Application Completed and Certified

Filed: 386 VAN BRUNT ST Census Tract:   53 Health Area:  4100
BAS,1,2,3,ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
DOB Cross Street(s):   WOLCOTT STREET,    DIKEMAN STREET
Status:   C - JOB IS SIGNED OFF 10/25/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/18/2013 10:18 PM
Application Entered:   07/18/2013 Job Start Date:   07/18/2013
Last Change:   10/25/2013 Job End Date:   07/18/2015
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     08/21/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012429 Licensee Name: TOMASZ STACHYRA
Firm: 004228 Firm Name: SOPOT ELECTRIC CORP
Firm Phone: 917-502-9722  Firm Address: 244 5TH AVENUE STE 2570 NEW YORK NY 10001 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $264.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL/RESIDENT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SCHLESSELAMAN DARIC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100A, 120/208
B. 101 Up to 200 AMPS  1  200A 120/208
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3-#2THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3-3/0 THHN
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20CKT, 120/208THHN
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1   34CKT, 120/208THHN
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    11    11             
001    23  13    12  23             
002    36  13    13  36             
003    28  15    19  28             
ROF      10         
Buildings Total 100  46    50  100     10           
Total Units : 306 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/18/2013 Notice: 1 - FIRST NOTICE 08/12/2013
Power Issued: 07/18/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B370284
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/08/2013 08/12/2013 CJH A E (50) (4) Y
INSPECTION COMMENTS: N
 
(2) 08/21/2013 08/30/2013 CJH C R E (26) (0) Y
INSPECTION COMMENTS: -

OBJECTION FOR APPLICATION #: B370284
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
NO POWER TO EXHAUST 110.2 1ST 2ND FL PANELS CIRCUITS NOT GROUPED210.4D
RSLV 08/08/2013 08/08/2013 08/21/2013
 
002 (999) OTHER
MULTI CONDUCTORS NEED SIMUTANEOUSLY DISCONNECTED 210.4B
RSLV 08/08/2013 08/08/2013 08/21/2013
 
003 (999) OTHER
CELLAR RECEPTICLES OUTLETS NOT TR 406.11
RSLV 08/08/2013 08/08/2013 08/21/2013
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
3RD FL LAUNDRY AREA 210.8
RSLV 08/08/2013 08/08/2013 08/21/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back