BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B369055
Premises: 283 ALBANY AVENUE BROOKLYN BIN: 3036946     Block: 1382   Lot: 4
   
Application Completed and Certified

Filed: 285 ALBANY AV Census Tract:   339
1,2,3,4,5,& 6 Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11213 Community Board:   308
DOB Cross Street(s):   ST JOHNS PLACE,    LINCOLN PLACE
Status:   C - JOB IS SIGNED OFF 07/10/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/13/2013 Job Start Date:   05/30/2013
Last Change:   07/10/2014 Job End Date:   12/31/2014
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     06/19/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010955 Licensee Name: ROMAN KATSNELSON
Firm: 000483 Firm Name: ENTERPRISES ELECTR CONTR
Firm Phone: 718-437-2700  Firm Address: 41 TERRACE PLACE INC BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,195.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   A - ADEQUATE WIRING PROGRAM
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARCUS GERSTAIN
Owner Business Name: STG MANAGEMENT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  53  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  5  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  53  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      16  16                 
002      18  18                 
003      18  18                 
004      18  18                 
005      18  18                 
006      18  18                 
Buildings Total   106  106                    
Total Units : 212 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 53 #4-Wire 1 #10-Wire 0
Existing Meters 56 + New Meters 54 - Removed Meters 54 = Total Meters 56

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/13/2013 Notice: 1 - FIRST NOTICE 05/19/2014
Power Issued: 06/13/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B369055
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/13/2014 05/19/2014 CJH A E (120) (5) Y
INSPECTION COMMENTS: INSPECTED APT 6B 60 6C 6J 64 54 5F 5E 5B
 
(2) 06/04/2014 06/09/2014 CJH J R E (220) (0) Y
INSPECTION COMMENTS: NO ACCESS TO APT 6 FL APT 6E 5A C4 AND ALL OTHER APTS
 
(3) 06/19/2014 06/23/2014 PAT C E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B369055
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR SVC SWITCH WHT CONDUCTOR TAPE GRN 200.7
RSLV 05/13/2014 05/13/2014 06/04/2014
 
002 (999) OTHER
CELLAR 600A SVC SWITCH DISSIMILAR FUSES
RSLV 05/13/2014 05/13/2014 06/04/2014
 
003 (999) OTHER
APT 6B 6C 6H MULTI CIR NEED COMMON TRIP 210.4B
RSLV 05/13/2014 05/13/2014 06/04/2014
 
004 (999) OTHER
APT 6B 6C 6H 5H 5F 5E 5J 5E PNL CIR NOT GROUPED 210.4D
RSLV 05/13/2014 05/13/2014 06/04/2014
 
005 (999) OTHER
APT 5H 5F 5J KO MISSING 110.14
RSLV 05/13/2014 05/13/2014 06/04/2014