BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B368951
Premises: 491 KEAP STREET BROOKLYN BIN: 3413996     Block: 2371   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 METROPOLITAN AV Census Tract:   513 Health Area:  0700
GROUND FLOOR - OUTDOOR Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    320373751
DOB Cross Street(s):   MEEKER AVENUE,    UNION AVENUE
Status:   C - JOB IS SIGNED OFF 07/10/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/12/2013 10:08 AM
Application Entered:   06/12/2013 Job Start Date:   06/12/2013
Last Change:   07/10/2018 Job End Date:   06/12/2015
Appointment Status:   
Last Inspection By:   OSCAR ZELAYA       On     07/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010255 Licensee Name: THOMAS ZIMMERMAN
Firm: 004025 Firm Name: FIRST QUALITY ELECT CORP
Firm Phone: 718-797-3518  Firm Address: 75 HUNGTINGTON STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
Total Fee:  $640.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SAL BOUSLEIMAN
Owner Business Name: NEW LINE STRUCTURES INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  600 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                       
Buildings Total                       
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/12/2013 Notice: 1 - FIRST NOTICE 07/30/2013
Power Issued: 06/12/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B368951
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2013 07/30/2013 EBA A E (40) (3) Y
INSPECTION COMMENTS: DID NOT COMPLETE INSPECTION
 
(2) 06/29/2018 07/02/2018 CJH N (60) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 07/09/2018 07/09/2018 OSZ C R (55) (0)
INSPECTION COMMENTS: ALL TEMP HAS BEEN REMOVED PRIOR TO INSPECTION, PREVIOUS OBJECTIONS NO LONGER EXIST.

OBJECTION FOR APPLICATION #: B368951
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) OUTSIDE NUMBER 2 GROUNDROD PROVIDED 250.56
RSLV 07/25/2013 07/25/2013 07/09/2018
 
002 (999) OTHER
(ALL FLOORS) OUTSIDE - NO W.R. GFI OUTSIDE 406.8
RSLV 07/25/2013 07/25/2013 07/09/2018
 
003 (999) OTHER
(ALL FLOORS) OUTSIDE NO BUBBLE COVER 406.8.B
RSLV 07/25/2013 07/25/2013 07/09/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.