BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B367928
Premises: 313 GRAFTON STREET BROOKLYN BIN: 3081977     Block: 3581   Lot: 16
   
Application Completed and Certified

Filed: 313 GRAFTON ST Census Tract:   894 Health Area:  5820
1ST & 2ND FLOORS Admin Area:   B - BROOKLYN Inspection Area:   H
BROOKLYN, NY 11212 Community Board:   316
Special Place Name:   MILLER RESIDENCE
DOB Cross Street(s):   LIVONIA AVENUE,    EAST 98 STREET
Status:   C - JOB IS SIGNED OFF 03/24/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/23/2013 7:42 AM
Application Entered:   05/23/2013 Job Start Date:   05/23/2013
Last Change:   03/24/2014 Job End Date:   07/31/2013
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     03/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009094 Licensee Name: J. ROBERT MANN, JR.
Firm: 000455 Firm Name: E-J ELEC. INSTALLATION CO
Firm Phone: 718-786-9400  Firm Address: 46-41 VERNON BLVD. LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $227.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DORCAS MILLER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  1 - #6, 3 - #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  3  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/24/2014 Notice: 1 - FIRST NOTICE 12/16/2013
Power Issued: 03/24/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB# AD/12-0100 REPLACING PERMIT #B311408 FILED BY ANOTHER CONTRACTOR- ECB VIOLATION#35009555M ISSUED TO OWNER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B367928
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/19/2013 12/03/2013 JSB N (15) (0) Y
INSPECTION COMMENTS: N
 
(2) 12/10/2013 12/16/2013 CJH A (15) (5) Y
INSPECTION COMMENTS: N
 
(3) 03/13/2014 03/24/2014 CLC C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B367928
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SVC GND ELECTRODE NOT CONFORM TO 250.64
RSLV 12/10/2013 12/10/2013 03/13/2014
 
002 (999) OTHER
SVC GND ROD NOT INSTALL 250.53 (D) (2)
RSLV 12/10/2013 12/10/2013 03/13/2014
 
003 (999) OTHER
SVC GND ELECTRODE NOT CONTINOUS CONDUIT ROTTEN 250.643E
RSLV 12/10/2013 12/10/2013 03/13/2014
 
004 (999) OTHER
CELLAR SVC SWITCH MIGB LUG LOOSE 250.92 (A)
RSLV 12/10/2013 12/10/2013 03/13/2014
 
005 (999) OTHER
CELLAR SVC SWITCH TWO CONDUCTOR ONE LUG 110.14
RSLV 12/10/2013 12/10/2013 03/13/2014