BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B367819
Premises: 763 3 AVENUE BROOKLYN BIN: 3009600     Block: 654   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 771 3 AV Census Tract:   101 Health Area:  4400
GROUND FL. Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11232 Community Board:   307
DOB Cross Street(s):    25 STREET,    26 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/20/2013 9:51 PM
Application Entered:   05/20/2013 Job Start Date:   05/20/2013
Last Change:   08/22/2025 Job End Date:   06/30/2013
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     02/19/2015      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010715 Licensee Name: TIMOTHY M MCDONALD
Firm: 001937 Firm Name: MAC ELECT'L CONTR. INC.
Firm Phone: 718-758-3500  Firm Address: 2807 FLATBUSH AVENUE BROOKLYN NY 11234 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   WOOD SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CENGIZ CAYGAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1   1| 200A S/S
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1   1| SET OF 3/0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1   1| 40C 200A PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  20    10  20             
Buildings Total 20  20    10  20                
Total Units : 70 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/20/2013 Notice: 1 - FIRST NOTICE 02/24/2015
Power Issued: 05/20/2013 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B367819
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/19/2015 02/24/2015 CCH V E (45) (6) Y
INSPECTION COMMENTS: WORK AREA NOW DIVIDED

OBJECTION FOR APPLICATION #: B367819
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 12) SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE
NEUTRAL UNDERSIZE LINE LOAD SER SW 400 AMP
OPEN 02/19/2015 02/19/2015
 
002 (999) OTHER
NEUTRAL BONDED IN DIS SW 250.24 A.5
OPEN 02/19/2015 02/19/2015
 
003 (999) OTHER
PLP USE AS RACEWAY TIME CLOCK 312.8
OPEN 02/19/2015 02/19/2015
 
004 (999) OTHER
OUTLETS MISSING NUT BOLT THROUGHOUT 406.4C
OPEN 02/19/2015 02/19/2015
 
005 (999) OTHER
CIR NOT GROUP 300.20
OPEN 02/19/2015 02/19/2015
 
006 (999) OTHER
MULTI CIR HANDLE TIES 210.4
OPEN 02/19/2015 02/19/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.