BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B367024
Premises: 364 BEDFORD AVENUE BROOKLYN BIN: 3063429     Block: 2443   Lot: 23
   
Application Completed and Certified

Filed: 120 S 4 ST Census Tract:   549 Health Area:  0500
SERVICE ROOM Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11249 Community Board:   301
Related Job Number:    302150231
DOB Cross Street(s):   BERRY STREET,    BEDFORD AVENUE
Status:   C - JOB IS SIGNED OFF 09/19/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/03/2013 8:36 AM
Application Entered:   05/03/2013 Job Start Date:   05/03/2013
Last Change:   09/19/2013 Job End Date:   03/01/2014
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     09/12/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012311 Licensee Name: MOSES ROSENBERGER
Firm: 004090 Firm Name: HIVOLTS ELECTRICAL INC
Firm Phone: 718-855-4346  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $901.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MAX SHTARK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  8  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  PLP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001              15         
Buildings Total              15           
Total Units : 15 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 20 #4-Wire 5 #10-Wire 0
Existing Meters 0 + New Meters 25 - Removed Meters 0 = Total Meters 25

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/03/2013 Notice: 1 - FIRST NOTICE 09/06/2013
Power Issued: 05/03/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B367024
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/18/2013 07/19/2013 JSB N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 08/01/2013 08/02/2013 JSB A E (90) (3) Y
INSPECTION COMMENTS: N
 
(3) 08/27/2013 09/06/2013 CJE A R E (25) (1) Y
INSPECTION COMMENTS: N
 
(4) 09/12/2013 09/17/2013 CJE C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B367024
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
PHASE BLOCKS USED IN TROUGH FOR COMMERCIAL METERS AND DISC SWITCHES
RSLV 08/01/2013 08/01/2013 08/27/2013
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO SUPPLIMENTAL GRD PROVIDED
RSLV 08/01/2013 08/01/2013 08/27/2013
 
003 (999) OTHER
600 AMP SVC COND OVER FUSED 310.16 COMMERCIAL METERING
RSLV 08/01/2013 08/01/2013 08/27/2013
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO GROUND FOR 30A FUSE CUT OUT SWITCH 250.24
RSLV 08/27/2013 08/27/2013 09/12/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back