Premises: 544 UNION AVENUE BROOKLYN BIN: 3413895     Block: 2736   Lot: 1
   
Application Completed and Certified

Filed: 544 UNION AV Census Tract:   515 Health Area:  0700
FLS 1-6, ROOF Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    302315368
DOB Cross Street(s):   UNION AVENUE,    LORIMER STREET
Status:   C - JOB IS SIGNED OFF 04/15/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/26/2013 1:54 PM
Application Entered:   04/26/2013 Job Start Date:   04/29/2013
Last Change:   04/15/2014 Job End Date:   12/31/2013
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     04/11/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011355 Licensee Name: CARMINE L LIPPOLIS
Firm: 002775 Firm Name: LIPPOLIS ELECTRIC, INC.
Firm Phone: 718-892-4055  Firm Address: 4459 BRONX BOULEVARD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 95 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MAHMOOD AFIFA
Owner Business Name: 544 UNIONCON LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  1  DISCONNECT SWITCH
C. 201 Up to 600 AMPS  2  FIRE PUMP
D. 601 Up to 1200 AMPS  4  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  96  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  17  
D. Over 250 MCM  12  4 WIRE, 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  95  3 WIRE, #1
C. 3 Phase Up to 225 AMPS  17  4 WIRE, 225AMPS, 42 CIRC
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    185  388    160  185  30  30     
002    260  388    160  260  30  20     
003    260  388    160  260  15         
004    260  388    160  260             
005    260  388    160  260             
006    260  388    160  260             
ROF    10  12    10             
Buildings Total 1495  2340    964  1495     75     50      
Total Units : 6419 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 95 #4-Wire 7 #10-Wire 2
Existing Meters 0 + New Meters 104 - Removed Meters 0 = Total Meters 104

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/26/2013 Notice: 1 - FIRST NOTICE 10/29/2013
Power Issued: 04/26/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRE NEW BUILDING. APARTMENTS AND RETAIL SPACE. (THIS IS ARE-FILING TO CORRECT THE ELECTRIC METER COUNT. ORIGINAL B# WAS B353861.)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B366798
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/22/2013 10/29/2013 PAT V E (315) (6) Y
INSPECTION COMMENTS: 2 - 1200A SER/SW INSTEAD OF 3, 2 SET OF 600 MCM INSTEAD OF 4 INDICATED ON DRAWING GOING TO RETAIL TROUGH AND MORE
 
(2) 11/25/2013 12/02/2013 PAT J Y E (135) (0) Y
INSPECTION COMMENTS: CALL# 51606, PENDING NEW DRAWING
 
(3) 03/11/2014 03/21/2014 PAT J Y E (180) (0) Y
INSPECTION COMMENTS: 2 SET OF 500MCM CABLE, 3-1200A SER, ONE FUSED AT 800AMP #2 AND #5 STILL REMAIN PENDING DRAWING
 
(4) 04/11/2014 04/15/2014 PAT C R E (15) (0) Y
INSPECTION COMMENTS: SIGN OFF ACCORDING TO NEW A/B DRAWING

OBJECTION FOR APPLICATION #: B366798
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
MANHOLE RING NOT BONDED 250.4, 250.110, 250.96
RSLV 10/22/2013 10/22/2013 11/25/2013
 
002 (999) OTHER
BASE WIRING NOT AS PER ADVISORY BOARD DRAWING
RSLV 10/22/2013 03/11/2014 04/11/2014
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
ENTIRE BLDGE NOT PROVIDED
RSLV 10/22/2013 10/22/2013 11/25/2013
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
RETAIL TROUGH
RSLV 10/22/2013 10/22/2013 11/25/2013
 
005 ( 19) DEFECTIVE WIRING IS IN USE
RETAIL TROUGH 6 METER INSTEAD OF 10 ON DRAWING
RSLV 10/22/2013 03/11/2014 04/11/2014
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
SOME OF THE GROUND IS UNDERSIZED, NOT SAME ON DRAWING
RSLV 10/22/2013 11/25/2013 03/11/2014