BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B366539
Premises: 23 CATON PLACE BROOKLYN BIN: 3124033     Block: 5320   Lot: 24
   
Application Completed and Certified

Filed: 23 CATON PL Census Tract:   504 Health Area:  5310
OCEAN PARKWAY Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11218 Community Board:   307
DOB Cross Street(s):   OCEAN PARKWAY,    EAST 8 STREET
Status:   C - JOB IS SIGNED OFF 05/18/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/19/2013 4:20 PM
Application Entered:   04/19/2013 Job Start Date:   04/22/2013
Last Change:   05/18/2015 Job End Date:   04/22/2014
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     05/11/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $623.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MOSHE FELLER
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  500.00
B. Each Additional 10 Floors Or Less  1  83.00
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/18/2015 Notice: 1 - FIRST NOTICE 03/04/2015
Power Issued: 05/18/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   NEW 4 OVERHEAD PASSENGER ELEVATORS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B366539
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/24/2015 03/04/2015 PAT V (30) (4) Y
INSPECTION COMMENTS: NOT FINAL
 
(2) 05/11/2015 05/18/2015 DAH C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B366539
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 42) BUSHINGS ARE MISSING OR LOOSE
ELEVATOR D.SW 300.11
RSLV 02/24/2015 02/24/2015 05/11/2015
 
002 (999) OTHER
TERMINATING GROUND SHOULD NOT BE USED FOR ANY OTHER PURPOSE 250.148
RSLV 02/24/2015 02/24/2015 05/11/2015
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUNDING CONDUCTORS NOT TERMINATED 250.112
RSLV 02/24/2015 02/24/2015 05/11/2015
 
004 (999) OTHER
NUMBER 14AWG WINE IS BEING USED FOR ALL ELEVATOR CAR LIGHTS DISCONNECT SWITCHES 210.19
RSLV 02/24/2015 02/24/2015 05/11/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back