BIS Menu  |  Plumb. Inspections  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B363553
Premises: 30 CLAVER PLACE BROOKLYN BIN: 3057297     Block: 1994   Lot: 37
   
Application Completed and Certified

Filed: 30 CLAVER PL Census Tract:   227 Health Area:  1300
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   303
DOB Cross Street(s):   JEFFERSON AVENUE,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 07/18/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/05/2013 11:36 PM
Application Entered:   03/05/2013 Job Start Date:   03/07/2013
Last Change:   07/18/2013 Job End Date:   03/01/2015
Appointment Status:   
Last Inspection By:   BANYA, E       On     07/10/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012311 Licensee Name: MOSES ROSENBERGER
Firm: 004090 Firm Name: HIVOLTS ELECTRICAL INC
Firm Phone: 718-855-4346  Firm Address: 21 HERKIMER PLACE BROOKLYN NY 11216 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $107.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 30-32 CLAVER PL LLC
Authorized Representative:  ZALMEN WAGSCHAL
Relationship To Owner:   PARTNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 9 + New Meters 1 - Removed Meters 0 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/05/2013 Notice: 1 - FIRST NOTICE 06/25/2013
Power Issued: 03/05/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B363553
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/17/2013 06/25/2013 HRB V D (25) (6) Y
INSPECTION COMMENTS: N
 
(2) 07/10/2013 07/15/2013 EBA C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B363553
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 12) SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE
FUSED AT 300 AMPS 2 SETS OF #2 FUSED AT 300
RSLV 06/17/2013 06/17/2013 07/10/2013
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BOND WIRE TO SMALL FROM ENDLINE BOX TO SERVICE SWITCH
RSLV 06/17/2013 06/17/2013 07/10/2013
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
SERVICE RACEWAY OUTSIDE
RSLV 06/17/2013 06/17/2013 07/10/2013
 
004 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
FROM SERVICE SWITCH TO WATER MAIN
RSLV 06/17/2013 06/17/2013 07/10/2013
 
005 (999) OTHER
SERVICE RACEWAY RAN IN HOLLOW SPACES (230.43 E)
RSLV 06/17/2013 06/17/2013 07/10/2013
 
006 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
2 SETS OF #2 FUSED AT 300 AMP
RSLV 06/17/2013 06/17/2013 07/10/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Property Profile  |  Electrical Inspection Work Order  |  Back