| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
2 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
|
| B. Over #2 to 1/0 |
1 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER MIGB MISSING BONDING SCREW |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 002 |
(999) |
OTHER NO UTILITY GROUND BAR 250.94 |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 003 |
(999) |
OTHER WATER GROUND NOT CONNECTED WITHIN 5FT OF VALVE 250.52 |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 004 |
( 19) |
DEFECTIVE WIRING IS IN USE FEED TO ROOF PANEL NO NEUTRAL IN BSMT |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 005 |
( 28) |
ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED FIXTURE OVER BAR NOT APPROVE |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 006 |
(999) |
OTHER ROOF OUTLET NOT BUBBLE COVER 4068B1 |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 007 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE NO BUSHING IN PULL BOX ON ROOF |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED OUTLET KITCHEN 1ST FL NOT GFCI (FOOD WARMERS) |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 009 |
( 19) |
DEFECTIVE WIRING IS IN USE LIGHT KITCHEN PLUG INSIDE CEILING COVER FOOD WARMERS |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 010 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED WIR NOT PROPERLY COLOUR IN PANEL |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |
| |
| 011 |
(999) |
OTHER GROUNDING TERMINAL NOT MACHINE SCREW 250.8A A3 |
RSLV |
10/08/2013 |
10/08/2013 |
11/15/2013 |