Electrical Application Details for App #: B361946
Premises: 267 FLATBUSH AVENUE BROOKLYN BIN: 3028027     Block: 1143   Lot: 1
   
Application Completed and Certified

Filed: 267 FLATBUSH AV Census Tract:   161 Health Area:  2600
BASEMENT & 1 FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11217 Community Board:   308
DOB Cross Street(s):    6 AVENUE,    ST MARKS AVENUE
Status:   C - JOB IS SIGNED OFF 03/18/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/14/2013 2:32 PM
Application Entered:   02/14/2013 Job Start Date:   02/14/2013
Last Change:   03/18/2014 Job End Date:   02/14/2016
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     11/15/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011089 Licensee Name: PIOTR WAS
Firm: 003040 Firm Name: ACP ELECTRICAL CONTRACTIN
Firm Phone: 212-541-4100  Firm Address: 412 WEST 48TH STREET, STE#1 NEW YORK NY 10036 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010540 JAKUBOWICZ, ADAM 003040 ACP ELECTRICAL CONTRACTIN RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $479.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JONATHAN A COHEN
Owner Business Name: BARMADON MANAGEMENT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    18  12    12  18         
001    62  63    28  62  18         
Buildings Total 80  75    40  80     21           
Total Units : 296 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 11 + New Meters 1 - Removed Meters 1 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/14/2013 Notice: 1 - FIRST NOTICE 10/15/2013
Power Issued: 02/14/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B361946
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/08/2013 10/15/2013 CCH V E (100) (11) Y
INSPECTION COMMENTS: CHECKING EVERYTHING
 
(2) 11/15/2013 11/25/2013 CLC C R E (5) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B361946
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
MIGB MISSING BONDING SCREW
RSLV 10/08/2013 10/08/2013 11/15/2013
 
002 (999) OTHER
NO UTILITY GROUND BAR 250.94
RSLV 10/08/2013 10/08/2013 11/15/2013
 
003 (999) OTHER
WATER GROUND NOT CONNECTED WITHIN 5FT OF VALVE 250.52
RSLV 10/08/2013 10/08/2013 11/15/2013
 
004 ( 19) DEFECTIVE WIRING IS IN USE
FEED TO ROOF PANEL NO NEUTRAL IN BSMT
RSLV 10/08/2013 10/08/2013 11/15/2013
 
005 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
FIXTURE OVER BAR NOT APPROVE
RSLV 10/08/2013 10/08/2013 11/15/2013
 
006 (999) OTHER
ROOF OUTLET NOT BUBBLE COVER 4068B1
RSLV 10/08/2013 10/08/2013 11/15/2013
 
007 ( 42) BUSHINGS ARE MISSING OR LOOSE
NO BUSHING IN PULL BOX ON ROOF
RSLV 10/08/2013 10/08/2013 11/15/2013
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
OUTLET KITCHEN 1ST FL NOT GFCI (FOOD WARMERS)
RSLV 10/08/2013 10/08/2013 11/15/2013
 
009 ( 19) DEFECTIVE WIRING IS IN USE
LIGHT KITCHEN PLUG INSIDE CEILING COVER FOOD WARMERS
RSLV 10/08/2013 10/08/2013 11/15/2013
 
010 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
WIR NOT PROPERLY COLOUR IN PANEL
RSLV 10/08/2013 10/08/2013 11/15/2013
 
011 (999) OTHER
GROUNDING TERMINAL NOT MACHINE SCREW 250.8A A3
RSLV 10/08/2013 10/08/2013 11/15/2013