Electrical Application Details for App #: B361665
Premises: 416 PACIFIC STREET BROOKLYN BIN: 3001135     Block: 190   Lot: 16
   
Application Completed and Certified

Filed: 416 PACIFIC ST Census Tract:   41 Health Area:  2400
THROUGHOUT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
Special Place Name:   THROUGHOUT
DOB Cross Street(s):   BOND STREET,    NEVINS STREET
Status:   C - JOB IS SIGNED OFF 04/22/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/11/2013 10:17 PM
Application Entered:   02/11/2013 Job Start Date:   02/15/2013
Last Change:   04/22/2013 Job End Date:   05/30/2013
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     04/15/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010731 Licensee Name: JAY G HELFGOTT
Firm: 003349 Firm Name: JAY HELFGOTT ELEC. CORP.
Firm Phone: 718-753-0091  Firm Address: 220 ASHFORD STREET BROOKLYN NY 11207 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $239.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARK SCHINER
Owner Business Name: B'KLYN HOLDING CORP.
Authorized Representative:  JAY HELFGOTT
Relationship To Owner:   LIC. ELECT. CONT'R.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-150A.,1-100AMP
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                   
BAS    12  20    12             
BAL                 
001    16  24    16             
002    22  20    22             
003    20  20    20             
Buildings Total 74  87    29  76                
Total Units : 266 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/11/2013 Notice: 1 - FIRST NOTICE 04/01/2013
Power Issued: 02/11/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL SERVICE AND PANELS IN APPROPRIATE PLACES,AND, LIGHTING AND OUTLETS AS DIRECTED.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B361665
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/12/2013 03/19/2013 HRB N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 03/28/2013 04/01/2013 HRB A D (65) (8) Y
INSPECTION COMMENTS: NEED TO RECHECK ALL CIRCUITS
 
(3) 04/15/2013 04/22/2013 HRB C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B361665
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BOTH SERVICE SWITCHES MUST HAVE GROUNDS TO THEM
RSLV 03/28/2013 03/28/2013 04/15/2013
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
OUTLET TO LOW IN 1ST FLOOR BATHROOM
RSLV 03/28/2013 03/28/2013 04/15/2013
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
FOR ALL OUTLETS THROUGHOUT HOUSE ALSO USING WRONG AFCI
RSLV 03/28/2013 03/28/2013 04/15/2013
 
004 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
BY FRIDGE IN KITCHEN
RSLV 03/28/2013 03/28/2013 04/15/2013
 
005 (999) OTHER
NEUTRAL BONDED IN AC SWITCHES IN BACK YARD (250.92)
RSLV 03/28/2013 03/28/2013 04/15/2013
 
006 (999) OTHER
NEED TAMPER AND WEATHER PROOF TYPE (406.8406.11)
RSLV 03/28/2013 03/28/2013 04/15/2013
 
007 (999) OTHER
ALL OUTLETS MUST BE TAMPER PROOF (406.11)
RSLV 03/28/2013 03/28/2013 04/15/2013
 
008 (999) OTHER
MULTIWIRE CIRCUIT NEED TWO POLE BREAKER (225.33B)
RSLV 03/28/2013 03/28/2013 04/15/2013