BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B359211
Premises: 4 DOUGLASS STREET BROOKLYN BIN: 3006643     Block: 414   Lot: 10
   
Application Completed and Certified

Filed: 285 COURT ST Census Tract:   75 Health Area:  2500
STORE Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
Special Place Name:   BAGEL SHOP
DOB Cross Street(s):   DOUGLASS STREET,    DEGRAW STREET
Status:   C - JOB IS SIGNED OFF 03/13/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/17/2013 6:16 AM
Application Entered:   01/17/2013 Job Start Date:   01/18/2013
Last Change:   03/13/2014 Job End Date:   04/05/2013
Appointment Status:   
Last Inspection By:   BANYA, E       On     11/06/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010482 Licensee Name: HARVEY ISAACMAN
Firm: 002810 Firm Name: ELECTRICAL SOLUTIONS LLC
Firm Phone: 718-788-2018  Firm Address: 145 30TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $244.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SIMON GERSHOVICH
Owner Business Name: COBBLE HILL BAGELS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP 3/0 THHN
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  1  40 CR.
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  25    12               
Buildings Total 20  25    12                  
Total Units : 57 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/17/2013 Notice: 1 - FIRST NOTICE 09/04/2013
Power Issued: 01/17/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B359211
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/01/2013 08/05/2013 CCH A E (75) (7) Y
INSPECTION COMMENTS: NO ACCESS TO ROOF
 
(2) 08/29/2013 09/04/2013 CCH A R E (55) (2) Y
INSPECTION COMMENTS: N
 
(3) 11/06/2013 11/12/2013 EBA C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B359211
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO WATER GROUND 2 TIME OUT OF END BOX
RSLV 08/01/2013 08/01/2013 08/29/2013
 
002 (999) OTHER
A SUPP GROUND RACEWAY NOT CONTINOUS 250.64
RSLV 08/01/2013 08/01/2013 08/29/2013
 
003 (999) OTHER
B NO UTILITY GROUND BAR 250.94
RSLV 08/01/2013 08/01/2013 08/29/2013
 
004 (999) OTHER
C EMT INSTALLED INSIDE HOOD 410.10
RSLV 08/01/2013 08/01/2013 08/29/2013
 
005 (999) OTHER
D GROUND BARS WITH SHEET ROCK SCREW 250.8.8.A.3
RSLV 08/01/2013 08/01/2013 08/29/2013
 
006 (999) OTHER
E CIRCUITS NOT GROUP IN PANEL 300.20
RSLV 08/01/2013 08/01/2013 08/29/2013
 
007 (999) OTHER
F OUTLET 30 AMP NOT 4 PIN BSMT 250.14
RSLV 08/01/2013 08/01/2013 08/29/2013
 
008 (999) OTHER
A NO UTILITY GROUND BAR 250.94
RSLV 08/29/2013 08/29/2013 11/06/2013
 
009 (999) OTHER
B SUPP GROUND RACEWAY NOT CONTINOUS 250.64
RSLV 08/29/2013 08/29/2013 11/06/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back