BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B357654
Premises: 25 PIERREPONT STREET BROOKLYN BIN: 3001728     Block: 234   Lot: 1
   
Application Completed and Certified

Filed: 152 WILLOW ST Census Tract:   3.01 Health Area:  2300
BAS Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   CLARK STREET,    PIERREPONT STREET
Status:   C - JOB IS SIGNED OFF 06/09/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/11/2012 6:45 AM
Application Entered:   12/11/2012 Job Start Date:   12/13/2012
Last Change:   06/09/2014 Job End Date:   03/21/2013
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     06/03/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $137.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ILAN TAVOR
Owner Business Name: 25PIERPONT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  6/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  24
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  34 CRT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/11/2012 Notice: C - CALL TO OFFICE 05/19/2014
Power Issued: 12/11/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B357654
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/28/2013 04/01/2013 HRB A D (20) (3) Y
INSPECTION COMMENTS: N
 
(2) 05/13/2014 05/19/2014 PAT H X E (0) (0) Y
INSPECTION COMMENTS: -
 
(3) 06/03/2014 06/09/2014 CLC C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B357654
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
ALL MAIN SERVICE SWITCH MUST HAVE GROUND TO THEM
RSLV 03/28/2013 05/13/2014 06/03/2014
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
NEED WATER METER JUMPER
RSLV 03/28/2013 05/13/2014 06/03/2014
 
003 (999) OTHER
DOUBLE LUGGING IN NEW SERVICE SWITCH (110.16)
RSLV 03/28/2013 05/13/2014 06/03/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.