BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B357014
Premises: 3096 BRIGHTON 6 STREET BROOKLYN BIN: 3245100     Block: 8689   Lot: 45
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 3096 BRIGHTON 6 ST Census Tract:   360.02 Health Area:  9110
BRIGHTWATER COURT Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11235 Community Board:   313
DOB Cross Street(s):   BRIGHTON BEACH AVENUE,    BRIGHTWATER COURT
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/27/2012 10:55 AM
Application Entered:   11/27/2012 Job Start Date:   11/27/2012
Last Change:   08/22/2025 Job End Date:   11/06/2013
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     10/24/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARTIN GELFAND
Owner Business Name: 3096 OWNERS CORP.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  125.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/28/2013 Notice: 1 - FIRST NOTICE 10/28/2013
Power Issued: 10/28/2013 Response:  

Follow-Up:
Contractor's Comments:   DEVICE NO. 3P2116

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B357014
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2013 07/01/2013 PAT A (30) (1) Y
INSPECTION COMMENTS: N
 
(2) 10/24/2013 10/28/2013 CJH A R E (50) (2) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B357014
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
MACHINE ROOM - ELEVATOR DISCONNECT SWITCH GROUND NOT CONNECTED
RSLV 06/27/2013 06/27/2013 10/24/2013
 
002 (999) OTHER
ELEVATOR PIT LIGHTS RECEPTICLE OUTLET SHARE CIR 620.24
OPEN 10/24/2013 10/24/2013
 
003 (999) OTHER
CELLAR MACHINE RM ELEVATOR CONTROLLER TWO LUGS ONE BOLT 110.14
OPEN 10/24/2013 10/24/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.