| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
2 |
1@3#2AWG 1@3#2/0AWG |
| C. Over 1/0 to 250 MCM |
1 |
1@3#4/0AWG |
| D. Over 250 MCM |
1 |
4#500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
2@60AMP 1@100AMP |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
1 |
400A/3P |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE WIRING STRING REMOVE FROM CABLE |
RSLV |
12/20/2012 |
12/20/2012 |
02/27/2013 |
| |
| 002 |
(999) |
OTHER SECOND GROUND ROD NEEDED 250.56 |
RSLV |
02/27/2013 |
02/27/2013 |
06/04/2013 |
| |
| 003 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH IN PANEL CONTACTOR 110.14 (A) |
RSLV |
02/27/2013 |
02/27/2013 |
06/04/2013 |
| |
| 004 |
(999) |
OTHER WHT CONDUCTOR NOT IDENTIFY IN PANEL CONTACTOR 200.6 |
RSLV |
02/27/2013 |
02/27/2013 |
06/04/2013 |
| |
| 005 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE BOOTS PANELS 300.11 |
RSLV |
02/27/2013 |
02/27/2013 |
06/04/2013 |
| |
| 006 |
(999) |
OTHER LIGHT POLE CIR CAMERA OCCUPIED SAME RACEWAY |
RSLV |
02/27/2013 |
02/27/2013 |
06/04/2013 |
| |
| 007 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE OUTSIDE - NEUTRAL NOT BONDED IN BOTH 400 AMP SERVICE SWITCHES |
RSLV |
06/04/2013 |
06/04/2013 |
06/24/2013 |
| |
| 008 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX OUTSIDE - 4" KO MISSING IN SERVICE SWITCH |
RSLV |
06/04/2013 |
06/04/2013 |
06/24/2013 |