BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B356974
Premises: 585 DEAN STREET BROOKLYN BIN: 3330632     Block: 1129   Lot: 81
   
Application Completed and Certified

Filed: 583 DEAN ST Census Tract:   163 Health Area:  2600
1 Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
Special Place Name:   BARCLAY ARENA PARKING LOT
Related Job Number:    320466946
DOB Cross Street(s):   CARLTON AVENUE,    VANDERBILT AVENUE
Status:   C - JOB IS SIGNED OFF 07/01/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/26/2012 3:57 PM
Application Entered:   11/26/2012 Job Start Date:   11/28/2012
Last Change:   07/01/2013 Job End Date:   03/31/2013
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     06/24/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011333 Licensee Name: STEVEN LAZZARO
Firm: 000648 Firm Name: HELLMAN ELECTRIC LLC
Firm Phone: 718-931-9900  Firm Address: 855 BRUSH AVENUE BRONX NY 10465 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $352.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320466946
Building Used As:   Z - Other
Store / Other:   PARKING LOT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ADAM SCHWARTZ
Owner Business Name: FOREST CITY RATNER
Authorized Representative:  THOMAS RUTTURA
Relationship To Owner:   GENERAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  1@3#2AWG 1@3#2/0AWG
C. Over 1/0 to 250 MCM  1  1@3#4/0AWG
D. Over 250 MCM  1  4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  2@60AMP 1@100AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400A/3P
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    47             
Buildings Total 47                
Total Units : 61 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/05/2013 Notice: 1 - FIRST NOTICE 06/10/2013
Power Issued: 03/05/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B356974
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2012 12/08/2012 CCH N (30) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 12/20/2012 12/24/2012 CCH V (70) (1) Y
INSPECTION COMMENTS: CHECK LIGHT POLE CIR TV SEPERATED RACEWAY 3 BOOTS NOT INSPECTED NOT ON FILE
 
(3) 02/27/2013 03/05/2013 CJH A R E (70) (5) Y
INSPECTION COMMENTS: N
 
(4) 06/03/2013 06/07/2013 JSB N (30) (0) Y
INSPECTION COMMENTS: N
 
(5) 06/04/2013 06/10/2013 RHO A R (90) (2) Y
INSPECTION COMMENTS: N
 
(6) 06/24/2013 07/01/2013 CJH C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B356974
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
WIRING STRING REMOVE FROM CABLE
RSLV 12/20/2012 12/20/2012 02/27/2013
 
002 (999) OTHER
SECOND GROUND ROD NEEDED 250.56
RSLV 02/27/2013 02/27/2013 06/04/2013
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
IN PANEL CONTACTOR 110.14 (A)
RSLV 02/27/2013 02/27/2013 06/04/2013
 
004 (999) OTHER
WHT CONDUCTOR NOT IDENTIFY IN PANEL CONTACTOR 200.6
RSLV 02/27/2013 02/27/2013 06/04/2013
 
005 ( 42) BUSHINGS ARE MISSING OR LOOSE
BOOTS PANELS 300.11
RSLV 02/27/2013 02/27/2013 06/04/2013
 
006 (999) OTHER
LIGHT POLE CIR CAMERA OCCUPIED SAME RACEWAY
RSLV 02/27/2013 02/27/2013 06/04/2013
 
007 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
OUTSIDE - NEUTRAL NOT BONDED IN BOTH 400 AMP SERVICE SWITCHES
RSLV 06/04/2013 06/04/2013 06/24/2013
 
008 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
OUTSIDE - 4" KO MISSING IN SERVICE SWITCH
RSLV 06/04/2013 06/04/2013 06/24/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back