Electrical Application Details for App #: B356515
Premises: 526 PENNSYLVANIA AVENUE BROOKLYN BIN: 3085056     Block: 3822   Lot: 31
   
Application Completed and Certified

Filed: 526 PENNSYLVANIA AV Census Tract:   1126 Health Area:  6300
ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   H
BROOKLYN, NY 11207 Community Board:   305
DOB Cross Street(s):   LIVONIA AVENUE,    RIVERDALE AVENUE
Status:   C - JOB IS SIGNED OFF 11/06/2014 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/17/2012 6:45 PM
Application Entered:   11/17/2012 Job Start Date:   11/20/2012
Last Change:   11/06/2014 Job End Date:   01/20/2013
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     08/25/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009968 Licensee Name: SIGMOND FRIED
Firm: 000558 Firm Name: FRIED ELECTRIC CO.
Firm Phone: 718-389-2141  Firm Address: 67 WEST STREET, UNIT 321 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,452.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MENACHEM M TIEFENBRUN
Owner Business Name: QUEENBEE CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  $105.00
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  32  $480.00
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  $75.00
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  32  $480.00
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    26  75  12  26  26             
002    26  75  12  26  26             
003    26  75  12  26  26             
004    26  75  12  26  26             
Buildings Total 112  301  48  108  112                
Total Units : 681 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 33 #4-Wire 0 #10-Wire 0
Existing Meters 33 + New Meters 33 - Removed Meters 33 = Total Meters 33

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/17/2012 Notice: 1 - FIRST NOTICE 07/14/2014
Power Issued: 11/17/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B356515
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/07/2014 03/10/2014 CCH V E (130) (21) Y
INSPECTION COMMENTS: NEED LOTS OF TIME FOR THIS JOB ALL APTS
 
(2) 04/23/2014 04/28/2014 PAT H X E (0) (0) Y
INSPECTION COMMENTS: UNDERSIZED BOND
 
(3) 05/09/2014 05/13/2014 CJH N (0) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(4) 05/20/2014 05/29/2014 PAT V X D (50) (6) Y
INSPECTION COMMENTS: NO ACCESS TO THE FIRST AND SECOND FL APT, FROM ONE TO SIXTEEN APT 28 27, 20 AND 21 OK. NO ACCESS TO THE BASE
 
(5) 06/11/2014 06/23/2014 PAT V Y G (195) (10) Y
INSPECTION COMMENTS: APT 2,3,5,6,7,8,10,11,12,13,19,20,21,23,24,27,28, AND 29 OKAY
 
(6) 07/10/2014 07/14/2014 CCH A R E (120) (2) Y
INSPECTION COMMENTS: N
 
(7) 08/25/2014 09/02/2014 CJE C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B356515
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A APTS BATHROOM ALL AC OUTLET GFCI NOT TAMPER PROOF 406.11
RSLV 03/07/2014 05/20/2014 06/11/2014
 
002 (999) OTHER
B BATHROOM GFCI ON KITCHEN HALLWAY CIRCUIT 210.11C3
RSLV 03/07/2014 05/20/2014 06/11/2014
 
003 (999) OTHER
C ALL CT OUTLET NOT GFCI 210.8A6
RSLV 03/07/2014 05/20/2014 06/11/2014
 
004 (999) OTHER
D ALL CT 12 NEED GFCI 210.52 C1
RSLV 03/07/2014 06/11/2014 07/10/2014
 
005 (999) OTHER
E ALL CT NEED TWO SEPERATED CIR 210.11C
RSLV 03/07/2014 06/11/2014 07/10/2014
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
ALL CIR NO ARC FAULT
RSLV 03/07/2014 05/20/2014 06/11/2014
 
007 (999) OTHER
F WITH HALLWAY NO OUTLET INSTALLED 210.52H
RSLV 03/07/2014 05/20/2014 06/11/2014
 
008 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
SMOKE DETECTOR NOT AN ARC FAULT
RSLV 03/07/2014 06/11/2014 07/10/2014
 
009 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
BED L/R NEED MORE OUTLETS
RSLV 03/07/2014 06/11/2014 07/10/2014
 
010 ( 19) DEFECTIVE WIRING IS IN USE
OUTLET THAT COVERED IN KITCHEN REMOVE WIRE ON BRAKER
RSLV 03/07/2014 05/20/2014 06/11/2014
 
011 (999) OTHER
G WATER GROUND RACEWAY NOT CONTINOUS 250.64C
RSLV 03/07/2014 05/20/2014 06/11/2014
 
012 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
WATER GROUND RACEWAY NOT PROPERLY SUPPORTED
RSLV 03/07/2014 05/20/2014 06/11/2014
 
013 ( 29) OUTLET BOXES ARE NOT COVERED
WATER GROUND LB COVER MISSING BOXES KO MISSING THROUGHOUT
RSLV 03/07/2014 05/20/2014 06/11/2014
 
014 (999) OTHER
H DOUBLE LUG IN NEUTRAL SER SW 110.14A
RSLV 03/07/2014 05/20/2014 06/11/2014
 
015 (999) OTHER
I NEUTRAL NOT BONDED TO FRAME 250.28
RSLV 03/07/2014 05/20/2014 06/11/2014
 
016 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PLP DIR
RSLV 03/07/2014 05/20/2014 06/11/2014
 
017 (999) OTHER
J NO LIGHT NEAR METERS 110.26
RSLV 03/07/2014 05/20/2014 06/11/2014
 
018 (999) OTHER
PLP NO MAIN BRAKER
RSLV 03/07/2014 05/20/2014 06/11/2014
 
019 (999) OTHER
L PLP CIR NOT GROUP 300.20
RSLV 03/07/2014 06/11/2014 07/10/2014
 
020 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
PLP 30 BRAKER ON #12 WIRE
RSLV 03/07/2014 05/20/2014 06/11/2014
 
021 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
HANGING CABLE NOT PROPERLY SUPPORTED THROUGHOUT
RSLV 03/07/2014 05/20/2014 06/11/2014
 
022 ( 19) DEFECTIVE WIRING IS IN USE
MC CABLE IN PANEL CUT
RSLV 05/20/2014 05/20/2014 06/11/2014
 
023 ( 53) GFCI HAS NOT BEEN PROVIDED
RIGHT SIDE OF SINK NO GFCI PROVIDED AND RIGHT OF STOVE
RSLV 05/20/2014 05/20/2014 06/11/2014
 
024 (999) OTHER
MULTIWIRE BRANCH NO HANDLE TIE PROVIDED 210.4D
RSLV 05/20/2014 06/11/2014 07/10/2014
 
025 (999) OTHER
BATHROOM CIRCUIT NOT DEDICATED 210.52
RSLV 05/20/2014 05/20/2014 06/11/2014
 
026 ( 53) GFCI HAS NOT BEEN PROVIDED
LEFT SIDE OF SINK
RSLV 05/20/2014 05/20/2014 06/11/2014
 
027 ( 42) BUSHINGS ARE MISSING OR LOOSE
RED BUSHING IS MISSING, WHITE TAPE IN PLACE OF BUSHING
RSLV 05/20/2014 05/20/2014 06/11/2014
 
028 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
APT. 1, 14, AND 15 IN LIVING ROOMS AND BEDROOMS ALSO APT 32
RSLV 06/11/2014 06/11/2014 07/10/2014
 
029 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
SMOKE DETECTOR NOT ON AFCI IN FOLLOWING APTS: 22, 14, 16, 9 AND APT1
RSLV 06/11/2014 06/11/2014 07/10/2014
 
030 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
APT 31, 22 AND 10 PANELS
RSLV 06/11/2014 06/11/2014 07/10/2014
 
031 ( 53) GFCI HAS NOT BEEN PROVIDED
LEFT SIDE OF SINK NO GFCI PROVIDED ALSO IN APT 30
RSLV 06/11/2014 06/11/2014 07/10/2014
 
032 ( 19) DEFECTIVE WIRING IS IN USE
NO TWO CIRCUIT PROVIDED ALSO IN APT 30
RSLV 06/11/2014 06/11/2014 07/10/2014
 
033 ( 53) GFCI HAS NOT BEEN PROVIDED
LEFT SIDE OF SINK
RSLV 06/11/2014 06/11/2014 07/10/2014
 
034 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
UNDERSIZED BOND IN 600 AMPS SER/SW
RSLV 06/11/2014 06/11/2014 07/10/2014
 
035 (999) OTHER
MULTIWIRE BRANCH CIRCUIT NOT HANDLETIE 210.4D
RSLV 06/11/2014 06/11/2014 07/10/2014
 
036 ( 53) GFCI HAS NOT BEEN PROVIDED
KIT COUNTER
RSLV 06/11/2014 06/11/2014 07/10/2014
 
037 ( 53) GFCI HAS NOT BEEN PROVIDED
LEFT OF SINK NO GFCI ALSO APT 17
RSLV 06/11/2014 06/11/2014 07/10/2014
 
038 (999) OTHER
WATER GROUND RACEWAY NOT CONTINOUS 250.64C
RSLV 07/10/2014 07/10/2014 08/25/2014
 
039 ( 29) OUTLET BOXES ARE NOT COVERED
WATER GROUND L.B COVER MISSING
RSLV 07/10/2014 07/10/2014 08/25/2014