BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B356487
Premises: 451 CLARKSON AVENUE BROOKLYN BIN: 3327711     Block: 4829   Lot: 1
   
Application Completed and Certified

Filed: 451 CLARKSON AV Census Tract:   808
KINGS COUNTY HOSPITAL-BLDG E Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   309
DOB Cross Street(s):   NEW YORK AVENUE,    EAST 37 STREET
Status:   C - JOB IS SIGNED OFF 06/02/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/16/2012 Job Start Date:   09/10/2012
Last Change:   06/02/2014 Job End Date:   12/25/2012
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     05/27/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010169 Licensee Name: JOHN RAGAVANIS
Firm: 003027 Firm Name: PJS ELECTRIC, INC.
Firm Phone: 347-306-5511  Firm Address: 2568 EAST 17TH STREET BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,406.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NYCH & HOSP CORP
Authorized Representative:  DANIEL GADIOMA
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  8  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS      15    10  11          300 
Buildings Total   15    10  11               300 
Total Units : 336 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/16/2012 Notice: C - CALL TO OFFICE 04/15/2014
Power Issued: 11/16/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B356487
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/07/2014 01/15/2014 PAT V E (60) (1) Y
INSPECTION COMMENTS: NEED MORE TIME FOR THIS JOB, NOT FINAL
 
(2) 03/04/2014 03/10/2014 CLC P (90) (0) Y
INSPECTION COMMENTS: CONTR NO SHOW UNABLE TO INSPECT
 
(3) 04/09/2014 04/15/2014 PAT V X E (90) (3) Y
INSPECTION COMMENTS: DID NOT INSPECT THE FEEDERS COMMING FROM THE GENERATOR TO THE ATS SWITCH, NOT FINAL
 
(4) 04/28/2014 05/07/2014 PAT N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(5) 05/27/2014 06/02/2014 CJE C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B356487
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FEEDERS DIAGRAM NOT PROVIDED 215.5 AMENDENT
RSLV 01/07/2014 04/09/2014 05/27/2014
 
002 (999) OTHER
NEUTRAL BAR IS NOT BONDED FOR SEPARATE DERIVED SYSTEM 250.20D
RSLV 04/09/2014 04/09/2014 05/27/2014
 
003 (999) OTHER
UNDERSIZED GROUNDING ELECTRODE 250.66
RSLV 04/09/2014 04/09/2014 05/27/2014
 
004 (999) OTHER
BONDING JUMPER FOR RACEWAY FOR SEPARATE DERIVED SYSTEM UNDERSIZED250.66
RSLV 04/09/2014 04/09/2014 05/27/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.