BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B355971
Premises: 1901 EMMONS AVENUE BROOKLYN BIN: 3326914     Block: 8775   Lot: 41
   
Application Completed and Certified

Filed: 1901 EMMONS AV Census Tract:   608 Health Area:  8721
BSMT Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
Special Place Name:   SERVICE
DOB Cross Street(s):   EAST 19 STREET,    OCEAN AVENUE
Status:   C - JOB IS SIGNED OFF 12/11/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/12/2012 3:53 PM
Application Entered:   11/12/2012 Job Start Date:   11/13/2012
Last Change:   12/11/2013 Job End Date:   12/31/2012
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     11/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011918 Licensee Name: LUKASZ TYKA
Firm: 003946 Firm Name: CENTRUM ELECTRIC CORP
Firm Phone: 917-543-9736  Firm Address: 12 LOMBARDY STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $865.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: LUNDYS MANAGEMENT LLC
Authorized Representative:  STEVE PAPPAS
Relationship To Owner:   MENAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  2500AMPS
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/12/2012 Notice: 1 - FIRST NOTICE 09/10/2013
Power Issued: 11/12/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RECOVERY WORK AFTER SANDY STORM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B355971
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/06/2013 09/10/2013 JSB A E (90) (6) Y
INSPECTION COMMENTS: N
 
(2) 11/22/2013 11/26/2013 CJE C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B355971
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GRD NOT INSTALLED
RSLV 09/06/2013 09/06/2013 11/22/2013
 
002 (999) OTHER
SUPPLEMENTAL GRD ELECTRODE NOT INSTALLED 250.53
RSLV 09/06/2013 09/06/2013 11/22/2013
 
003 (999) OTHER
METAL TROUGH FLANGE NOT PROPERLY INSTALLED 110.3 (B)
RSLV 09/06/2013 09/06/2013 11/22/2013
 
004 (999) OTHER
SVC ENT COND NOT FULLY RATED FOR SVC SW 230.42
RSLV 09/06/2013 09/06/2013 11/22/2013
 
005 (999) OTHER
HOUSE DIST PNL PARELLEL 300KCMIL OVER FUSED 310.15(B)
RSLV 09/06/2013 09/06/2013 11/22/2013
 
006 (999) OTHER
1200 AMP DIST PNL EQUIPT GRD UNDERSIZED 250.122
RSLV 09/06/2013 09/06/2013 11/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.