BIS Menu  |  Applications  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B355541
Premises: 501 BRIGHTWATER COURT BROOKLYN BIN: 3245102     Block: 8689   Lot: 97
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 501 BRIGHTWATER COURT Census Tract:   360.02 Health Area:  9110
BRIGHTON 5TH STREET Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11235 Community Board:   313
DOB Cross Street(s):   BRIGHTON 5 STREET,    BRIGHTON 6 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/06/2012 3:47 PM
Application Entered:   11/06/2012 Job Start Date:   11/06/2012
Last Change:   08/22/2025 Job End Date:   11/06/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     01/23/2015      
Field Disp:   H - NO PROGRESS ON JOB
Energize Recommendation:  
Objection Disposition:  X - NOT REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: URI MR.
Owner Business Name: GAMMA REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 01/29/2015
Power Issued: Response:  

Follow-Up:
Contractor's Comments:   DEVICE NO. 3P1833 & 3P1834

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B355541
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/13/2013 06/18/2013 CJE V (50) (7) Y
INSPECTION COMMENTS: HURRICANE SANDY. HAD OVER 15-20 FEET OF WATER
 
(2) 08/05/2014 08/12/2014 JTE V R (45) (7) Y
INSPECTION COMMENTS: ALL EQUIPMENT FROM ELEV PIT, MECH ROOM MUST BE REPLACED + BROUGHT UP TO CODE, NOT A FINAL
 
(3) 01/23/2015 01/29/2015 JTE H X (0) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B355541
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (250) NO OTHER CONDUCTORS IN RACEWAY
BSMT. LINE & LOAD SAME 110 RACEWAY FOR BOTH ELEVATOR. ART 230.7
RSLV 06/13/2013 06/13/2013 08/05/2014
 
002 (220) DOUBLE LUGGING IN SERVICE SWITCH
BSMT.GROUND CONDUCTOR DOUBLE LUGGED ON CONTROLLER FRAME ELEVATORS(BOTH) ART 110.14(A)
RSLV 06/13/2013 06/13/2013 08/05/2014
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
GROUND CONDUCTOR DOUBLE LUGGED 110 DISCONNECT FOR ELEVATOR 381833ART. 110.14 (A)
RSLV 06/13/2013 06/13/2013 08/05/2014
 
004 ( 19) DEFECTIVE WIRING IS IN USE
BSMT. NO NEUTRAL PROVIDE IN DISCONNECT SWITCH 3P1834. AMEND 110.14 A
RSLV 06/13/2013 06/13/2013 08/05/2014
 
005 (999) OTHER
BSMT. RECEPTACLE FOR SUMP PUMPS NOT PROVIDED
RSLV 06/13/2013 06/13/2013 08/05/2014
 
006 ( 19) DEFECTIVE WIRING IS IN USE
BSMT. GROUND LUGGS DEFECTIVE AMEND 110.2(A)
RSLV 06/13/2013 06/13/2013 08/05/2014
 
007 ( 19) DEFECTIVE WIRING IS IN USE
BSMT. FEEDER WIRE DEFECTIVE AMEND 110.2 (2)
RSLV 06/13/2013 06/13/2013 08/05/2014
 
008 (999) OTHER
ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR CAR LIGHTS 62022A
OPEN 08/05/2014 01/23/2015
 
009 (999) OTHER
ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR ALL MACHINE ROOM, SPACE LIGHTING + RECEPTACLES 620.23A
OPEN 08/05/2014 01/23/2015
 
010 (999) OTHER
ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR HOISTWAY PIT LIGHT + RECEPTACLES 620.24A
OPEN 08/05/2014 01/23/2015
 
011 (999) OTHER
BSMT SUMP PUMP RECEPTACLE NOT ON DEDICATED LINE 620.25A
OPEN 08/05/2014 01/23/2015
 
012 (999) OTHER
BOTH ELEV LIGHTING DISC/SW NO NEUTRAL PROVIDED 110.14A
OPEN 08/05/2014 01/23/2015
 
013 (999) OTHER
BOTH ELE MOTOR DISC/SW LINE SIDE FEEDERS COMPRIMISE BY SALT WATER
OPEN 08/05/2014 01/23/2015
 
014 (999) OTHER
ALL EXISTING CONDUCTORS, FEEDERS + RACEWAY IN BSMT AND ELEV PIT HADBEEN COMPRIMISED BY SALT WATER 110.11
OPEN 08/05/2014 01/23/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Property Profile  |  Electrical Inspection Work Order  |  Back