| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
250.00 |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(250) |
NO OTHER CONDUCTORS IN RACEWAY BSMT. LINE & LOAD SAME 110 RACEWAY FOR BOTH ELEVATOR. ART 230.7 |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 002 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH BSMT.GROUND CONDUCTOR DOUBLE LUGGED ON CONTROLLER FRAME ELEVATORS(BOTH) ART 110.14(A) |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 003 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH GROUND CONDUCTOR DOUBLE LUGGED 110 DISCONNECT FOR ELEVATOR 381833ART. 110.14 (A) |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 004 |
( 19) |
DEFECTIVE WIRING IS IN USE BSMT. NO NEUTRAL PROVIDE IN DISCONNECT SWITCH 3P1834. AMEND 110.14 A |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 005 |
(999) |
OTHER BSMT. RECEPTACLE FOR SUMP PUMPS NOT PROVIDED |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE BSMT. GROUND LUGGS DEFECTIVE AMEND 110.2(A) |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 007 |
( 19) |
DEFECTIVE WIRING IS IN USE BSMT. FEEDER WIRE DEFECTIVE AMEND 110.2 (2) |
RSLV |
06/13/2013 |
06/13/2013 |
08/05/2014 |
| |
| 008 |
(999) |
OTHER ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR CAR LIGHTS 62022A |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 009 |
(999) |
OTHER ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR ALL MACHINE ROOM, SPACE LIGHTING + RECEPTACLES 620.23A |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 010 |
(999) |
OTHER ELEV #'S 3P1833, 3P1834 NO SEPARATE CKT PROVIDED FOR HOISTWAY PIT LIGHT + RECEPTACLES 620.24A |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 011 |
(999) |
OTHER BSMT SUMP PUMP RECEPTACLE NOT ON DEDICATED LINE 620.25A |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 012 |
(999) |
OTHER BOTH ELEV LIGHTING DISC/SW NO NEUTRAL PROVIDED 110.14A |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 013 |
(999) |
OTHER BOTH ELE MOTOR DISC/SW LINE SIDE FEEDERS COMPRIMISE BY SALT WATER |
OPEN |
08/05/2014 |
01/23/2015 |
|
| |
| 014 |
(999) |
OTHER ALL EXISTING CONDUCTORS, FEEDERS + RACEWAY IN BSMT AND ELEV PIT HADBEEN COMPRIMISED BY SALT WATER 110.11 |
OPEN |
08/05/2014 |
01/23/2015 |
|