BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B355128
Premises: 113 SOUTH 4 STREET BROOKLYN BIN: 3063255     Block: 2430   Lot: 32
   
Application Completed and Certified

Filed: 113 S 4 ST Census Tract:   551 Health Area:  0400
BSMT,1 ST FL, 2ND FL, 3RD FL Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11249 Community Board:   301
Related Job Number:    320409937
DOB Cross Street(s):   BERRY STREET,    BEDFORD AVENUE
Status:   C - JOB IS SIGNED OFF 05/07/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/18/2012 1:46 PM
Application Entered:   10/18/2012 Job Start Date:   10/18/2012
Last Change:   05/07/2015 Job End Date:   10/17/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     05/06/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $171.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRED ALVAREZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15         
001    15             
002    20         
003    20         
Buildings Total 26  70  10  28  28     12           
Total Units : 174 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/07/2015 Notice: 1 - FIRST NOTICE 04/28/2015
Power Issued: 05/07/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR 3 APARTMENTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B355128
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/27/2015 03/30/2015 EBA V (40) (2) Y
INSPECTION COMMENTS: A/C COMPRESSORS NOT IN PLACE
 
(2) 04/22/2015 04/28/2015 EBA A R (30) (1) Y
INSPECTION COMMENTS: N
 
(3) 05/06/2015 05/07/2015 JSB C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B355128
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FIXTURES NOT DAMP LOCATION APPROVED (410.10)(A)
RSLV 03/27/2015 03/27/2015 04/22/2015
 
002 (999) OTHER
MULTI CIRCUITS NOT GROUPED (210.4)(D)
RSLV 03/27/2015 03/27/2015 04/22/2015
 
003 (999) OTHER
SERVICE OUTLET NOT PROVIDED AT COMPRESSOR (210.63)
RSLV 04/22/2015 04/22/2015 05/06/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.