BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B355003
Premises: 380 VAN BRUNT STREET BROOKLYN BIN: 3008606     Block: 575   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 380 VAN BRUNT ST Census Tract:   53
CELLAR,1F,2F,3F Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
DOB Cross Street(s):   WOLCOTT STREET,    DIKEMAN STREET
Status:   C - JOB IS SIGNED OFF 12/25/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/15/2012 Job Start Date:   10/05/2012
Last Change:   12/25/2018 Job End Date:   12/20/2012
Appointment Status:   
Last Inspection By:   OSCAR ZELAYA       On     12/22/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $429.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320466526
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STANFORD CHAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    16  15    10  16             
001    20  24    15  20  10         
002    20  20    10  20         
003    20  28    10  20         
Buildings Total 76  87    45  76     20           
Total Units : 304 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 0
Existing Meters 2 + New Meters 3 - Removed Meters 2 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/15/2012 Notice: 1 - FIRST NOTICE 12/01/2018
Power Issued: 10/15/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B355003
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/01/2018 12/01/2018 CJH V (87) (7)
INSPECTION COMMENTS: FAIL
 
(2) 12/22/2018 12/22/2018 OSZ C R (20) (0)
INSPECTION COMMENTS: ALL OBJECTIONS HAVE BEEN RESOLVED.

OBJECTION FOR APPLICATION #: B355003
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) 001 FL PNL CKT BREAKERS NOT PER MFG LISTING 110.2
RSLV 12/01/2018 12/01/2018 12/22/2018
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) OCP FOR AC UNITS NOT PROPERLY SIZE 240.3
RSLV 12/01/2018 12/01/2018 12/22/2018
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) PNLS NOT PROPERLY LABEL 408.4
RSLV 12/01/2018 12/01/2018 12/22/2018
 
004 (999) OTHER
(GROUND FLOOR) GND FL DISHWASHER CKT NOT PROVIDED 210.52 B
RSLV 12/01/2018 12/01/2018 12/22/2018
 
005 (999) OTHER
(GROUND FLOOR) GND FL KO MISSING 110.12
RSLV 12/01/2018 12/01/2018 12/22/2018
 
006 (999) OTHER
(GROUND FLOOR) GND FL PNL CKT NOT GROUPED 210.4D
RSLV 12/01/2018 12/01/2018 12/22/2018
 
007 (999) OTHER
(ROOF) ROOF AC UNITS DIS-SWITCH NOT LABEL 110.22
RSLV 12/01/2018 12/01/2018 12/22/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.