BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B354787
Premises: 736 FRANKLIN AVENUE BROOKLYN BIN: 3324387     Block: 1168   Lot: 60
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 736 FRANKLIN AV Census Tract:   217 Health Area:  2720
1 Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   PARK PLACE,    STERLING PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/05/2012 1:58 PM
Application Entered:   10/05/2012 Job Start Date:   10/08/2012
Last Change:   08/22/2025 Job End Date:   12/23/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     04/03/2014      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 012067 Licensee Name: MICHAEL K PETERSON
Firm: 003761 Firm Name: MKP ELECTRIC CORP
Firm Phone: 718-783-0103  Firm Address: 733 FRANKLIN AVENUE BROOKLYN NY 11238 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $355.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 3 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARTURO LEONAR
Owner Business Name: ARTURO LEONAR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  400AMP DISCONNECT
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  4#500KCMIL
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/05/2012 Notice: 1 - FIRST NOTICE 04/07/2014
Power Issued: 10/05/2012 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B354787
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/03/2014 04/07/2014 CCH A E (40) (6) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B354787
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
400 AMP SER SW LOCK NUT NOT SECURE
OPEN 04/03/2014 04/03/2014
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
400 AMP NO GROUND INSTALLED
OPEN 04/03/2014 04/03/2014
 
003 (999) OTHER
A NO UTILITY BAR INSTALL 250.94
OPEN 04/03/2014 04/03/2014
 
004 (999) OTHER
B NO ACCESS TO TROUGH 1.2 314.29
OPEN 04/03/2014 04/03/2014
 
005 (999) OTHER
C NEUTRAL BONDED IN 42 CIR PANEL 250.24A
OPEN 04/03/2014 04/03/2014
 
006 (999) OTHER
D RACEWAY TO WATER PIPE NOT CONTINOUS 250.64E
OPEN 04/03/2014 04/03/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.