| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER CELLAR FLOORS PNL CIR NOT GROUPED 210.4D |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 002 |
(999) |
OTHER CELLAR PNLS CIR NOT SIMUTANEOUSLY DISCONNECTED 210.4B |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 003 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX CELLAR SUB PNL KO MISSING 110.12A |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED CELLAR SUB PNL GRN CONDUCTOR 250.112 |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 005 |
(999) |
OTHER ALL FLS THROUGHOUT GFCI RECEPTICLE OUTLETS NOT TR 406.11 |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 006 |
(999) |
OTHER 1ST FL BATHROOM BRANCH CIR NOT PROVIDED 210.52 (C3) |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 007 |
(999) |
OTHER 1ST FL BATHROOM KITCHEN COUNTER RECEPTICLES SAME CIR 210.52 (B2) |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 008 |
( 29) |
OUTLET BOXES ARE NOT COVERED 1ST FL REAR BEDROOM RIGHT SIDE 314.25 |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 009 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS 1ST FL LIVING ROOM AMEND 210.52 (1) |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |
| |
| 010 |
(999) |
OTHER 1ST FL AFCI PROTECTION NOT PROVIDED THROUGHOUT 210.12B |
RSLV |
12/10/2013 |
12/10/2013 |
03/13/2014 |