| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
1600 AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
4 |
# 2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
4/0 |
| D. Over 250 MCM |
4 |
600 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
6 |
(4) 100 AMP (2) 225 AMP |
| D. 3 Phase Over 225 AMPS |
1 |
1600 AMP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER NO FUSE COORDINATION OVER 160V 240.12 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 002 |
(999) |
OTHER THROUGHOUT CIR NOT GROUPED 210.4D |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 003 |
(999) |
OTHER CELLAR GND ELECTRODE RACEWAY NOT CONTINOUS 250.64 (3) (E) |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 004 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX CELLAR POOL MECHANICAL ROOM TROUGH 110.12A |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 005 |
(999) |
OTHER CELLAR POOL MECHANICAL ROOM MULTI CIR NEED 2 POLE BRAKERS 210.14B |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED OUTSIDE LOWER ROOF AC UNITS GND 250.112 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 007 |
(999) |
OTHER OUTSIDE THROUGHOUT BUBBLE COVER MISSING 406.8 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 008 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE 2ND FL MECHANICAL ROOM DIS SW 15 NEEDED 240.3 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 009 |
(999) |
OTHER OUTSIDE UPPER ROOF COOLER CONDENSER DIS SW LUG 2 COND 110.14 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 010 |
(999) |
OTHER ROOF MECHANICAL ROOM GFCI NOT INSTALLED 210.8 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 011 |
(999) |
OTHER OUTSIDE UPPER ROOF COOLER DIS SW SELF TAPE SCREW 250.8 |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 012 |
(999) |
OTHER TEMP WIRE THROUGHOUT 590.3B |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |
| |
| 013 |
(999) |
OTHER GFCI PROTECTION NEEDED FOR POOL PUMP MOTOR BRANCH CIR SPECIALBREAKER 680.22 (B) |
RSLV |
04/03/2014 |
04/03/2014 |
04/22/2014 |