BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
0 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
0 |
|
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE (OPEN SPACE) GND ROD HAS NOT BEEN PROVIDED FOR SHED. AMEND. 590.8(6) |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
002 |
(167) |
METALLIC EQUIPMENT IS NOT PROPERLY BONDED (OPEN SPACE)SECTIONS OF SHED ARE NOT BONDED TOGETHER. AMEND. 590.8(6) |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (OPEN SPACE) SEAL TIGHT IS NOT SUPPORTED. ART. 350.30(A) |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
004 |
(222) |
USING NON METALLIC SEALTITE NOT APPROVED (OPEN SPACE)NON-METALLIC SEAL TIGHT ABOVE FRONT OUTDOOR ENTRY. AMEND. 356.10 |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
005 |
( 30) |
OUTLET BOXES ARE NOT SECURED (OPEN SPACE) LIGHTING OUTLETS ARE NOT SUPPORTED. ART. 314.23 |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
006 |
(310) |
SEALTIGHT IS OF EXCESSIVE LENGTH (OPEN SPACE) OVER 6FT OF SEAL TIGHT. AMEND. 350.10 |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
007 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (OPEN SPACE) KO IS LIGHTING OUTLETS. ART. 110.12(A) |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (OPEN SPACE)GFCI PROTECTION HAS NOT BEEN PROVIDED FOR LIGHTING CKT. AMEND.590.8(5) |
OPEN |
06/22/2022 |
06/22/2022 |
|
|
009 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) (OPEN SPACE) TYPE IMC IS NOT SUPPORTED T-OUT. ART. 342.30 |
OPEN |
06/22/2022 |
06/22/2022 |
|