BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B351678
Premises: 22 MONTGOMERY PLACE BROOKLYN BIN: 3024995     Block: 1073   Lot: 15
   
Application Completed and Certified

Filed: 22 MONTGOMERY PL Census Tract:   165
1 Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    8 AVENUE,    PROSPECT PARK WEST
Status:   C - JOB IS SIGNED OFF 09/22/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/03/2012 8:39 AM
Application Entered:   07/03/2012 Job Start Date:   07/03/2012
Last Change:   09/22/2015 Job End Date:   07/30/2012
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     04/13/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011111 Licensee Name: ALAN RIBACK
Firm: 002475 Firm Name: ELECTRICAL SECURITY CORP.
Firm Phone: 718-284-0920  Firm Address: 69 VAN DAM STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRYAN GOLDSTEIN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND                 
Buildings Total                     
Total Units : 2 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/20/2015 Notice: 1 - FIRST NOTICE 06/16/2014
Power Issued: 04/20/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  110V WIRING FOR 1 SPLIT A/C IN THE REAR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B351678
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2014 06/16/2014 EBA A (30) (2) Y
INSPECTION COMMENTS: N
 
(2) 09/10/2014 09/16/2014 HRB N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS, NO SHOW
 
(3) 09/26/2014 09/29/2014 DAH N (15) (0) Y
INSPECTION COMMENTS: CONT NO SHOW
 
(4) 04/13/2015 04/20/2015 CJH C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B351678
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GFI OUTSIDE NOT W.R. 406.8.B
RSLV 06/12/2014 06/12/2014 04/13/2015
 
002 (999) OTHER
WIRE TAPED AT COMPRESSOR 200.6
RSLV 06/12/2014 06/12/2014 04/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back