BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B351412
Premises: 1240 EAST 38 STREET BROOKLYN BIN: 3209123     Block: 7637   Lot: 49
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1240 E 38 ST Census Tract:   738 Health Area:  8810
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   Q
BROOKLYN, NY 11210 Community Board:   318
DOB Cross Street(s):   FLATBUSH AVENUE,    AVENUE L
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   08/09/2012 Job Start Date:   08/09/2012
Last Change:   08/22/2025 Job End Date:   02/20/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     11/29/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012301 Licensee Name: AARON LEBOVITS
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012302 WEBER, MAYER 004070 METRO ELEC'L CONTRS, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $94.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 1240 EAST 38TH STREET COR
Authorized Representative:  R BAUE
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/03/2012
Power Issued: Response: F - FILED TO REMOVE OBJECTION 08/09/2012

Follow-Up: F - FILED TO REMOVE OBJECTION 08/09/2012
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B351412
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/16/2012 06/25/2012 KAS W (15) (4)
INSPECTION COMMENTS: -
 
(2) 11/29/2012 12/03/2012 PAT A Y (60) (0) Y
INSPECTION COMMENTS: #11,#36 & #19 STILL REMAIN

OBJECTION FOR APPLICATION #: B351412
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
FOR BRANCK CIRCUIT, BOILER, PANEL & FEEDER
RSLV 06/16/2012 06/16/2012 11/29/2012
 
002 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE, BOILER ROON C.B. PANEL215.2(AJ)
OPEN 06/16/2012 11/29/2012
 
003 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
CONDUCTORS ARE NOT PROPERLY #12 AWG WHITE WIRE MARKED WITH TAPE
OPEN 06/16/2012 11/29/2012
 
004 ( 19) DEFECTIVE WIRING IS IN USE
DEFECTIVE WIRING IS IN USE,PANEL FEEDER DOUBLE LUGGED 110. 14 1A
OPEN 06/16/2012 11/29/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back