BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B350940
Premises: 510 AVENUE N BROOKLYN BIN: 3173765     Block: 6587   Lot: 6
   
Application Completed and Certified

Filed: 510 AV N Census Tract:   440 Health Area:  7120
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   312
DOB Cross Street(s):   EAST 5 STREET,    OCEAN PARKWAY
Status:   C - JOB IS SIGNED OFF 02/08/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/12/2012 8:40 AM
Application Entered:   06/12/2012 Job Start Date:   06/12/2012
Last Change:   02/08/2013 Job End Date:   06/12/2012
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     09/12/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011444 Licensee Name: STEVEN FARKAS
Firm: 002896 Firm Name: STEVEN FARKAS
Firm Phone: 718-612-5490  Firm Address: 42 RICHMOND TERRACE STATEN ISLAND NY 10301 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $152.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: J SROUR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 A/ MAIN BREAKER PANEL
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 THHN
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  42 CKT PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/12/2012 Notice: 1 - FIRST NOTICE 07/30/2012
Power Issued: 06/12/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 200 AMP METER PAN. INSTALL 2'' CONDUIT TO FEED METER PAN. INSTALL 2'' CONDUIT TO FEED EXISTING MAIN BREAKER PANEL.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B350940
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2012 07/30/2012 JMZ A E (45) (5) Y
INSPECTION COMMENTS: N
 
(2) 09/12/2012 09/17/2012 JMZ C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B350940
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
3 WIRE CURCUITS NEED 2 POLE BREAKERS BASEMENNT PANEL
RSLV 07/25/2012 07/25/2012 09/12/2012
 
002 (999) OTHER
GROUP 3 WIRE CIRCUIT BASEMENT PANEL 210.4(D)
RSLV 07/25/2012 07/25/2012 09/12/2012
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT PANEL KO'S MISSING
RSLV 07/25/2012 07/25/2012 09/12/2012
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT PANEL TAPE UNDER BX CONNECTORS
RSLV 07/25/2012 07/25/2012 09/12/2012
 
005 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
SERVICE ROOM SUPPORT BX
RSLV 07/25/2012 07/25/2012 09/12/2012