Electrical Application Details for App #: B350557
Premises: 229 CARLTON AVENUE BROOKLYN BIN: 3397450     Block: 2090   Lot: 21
   
Application Completed and Certified

Filed: 229 CARLTON AV Census Tract:   183
ENTIRE BLDG Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11205 Community Board:   302
Related Job Number:    320314904
DOB Cross Street(s):   WILLOUGHBY AVENUE,    DEKALB AVENUE
Status:   C - JOB IS SIGNED OFF 09/06/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/30/2012 11:34 PM
Application Entered:   05/30/2012 Job Start Date:   05/30/2012
Last Change:   09/06/2014 Job End Date:   03/29/2013
Appointment Status:   
Last Inspection By:   BANYA, E       On     08/26/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011041 Licensee Name: SALVATORE CHIARAMONTE
Firm: 003893 Firm Name: L&B ELEC'L INTERNATIONAL
Firm Phone: 347-295-0380  Firm Address: 150-50 11TH AVENUE WHITESTONE NY 11357 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $304.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL RUBINSTEIN
Owner Business Name: PROFESSIONAL GRADE CONSTR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  PNL A 1ST FL
B. 101 Up to 200 AMPS  1  HOUSE PNL
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  PNL A
B. Over #2 to 1/0  1  HOUSE PNL
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  SUB HOUSE PNL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  PNL A & HOUSE PNL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10           
GND  OUTSI                 
001    20  20    13  15         
002    26  23    16  15         
003    21  16    14  15         
004    22  19    12  15         
ROF        34         
Buildings Total 99  90    60  70     56           
Total Units : 375 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/30/2012 Notice: 1 - FIRST NOTICE 08/11/2014
Power Issued: 05/30/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B350557
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/22/2013 03/27/2013 HRB J E (50) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT READY AND WONT BE READY FOR ABOUT A YEAR
 
(2) 07/25/2014 07/28/2014 CCH A E (30) (5) Y
INSPECTION COMMENTS: N
 
(3) 08/07/2014 08/11/2014 CJE A R E (25) (2) Y
INSPECTION COMMENTS: N
 
(4) 08/26/2014 08/27/2014 EBA C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B350557
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
DOUBLE SINK 3.4 FL NEED TWO GFCI
RSLV 07/25/2014 07/25/2014 08/07/2014
 
002 ( 19) DEFECTIVE WIRING IS IN USE
OUTLET OVER STOVE MOVE TO C.T
RSLV 07/25/2014 07/25/2014 08/07/2014
 
003 (999) OTHER
LIGHT OVER TUB NOT DAMPER PROOF 410
RSLV 07/25/2014 07/25/2014 08/07/2014
 
004 (999) OTHER
CIR NOT GROUP IN PANELS THROUGHOUT 300.20
RSLV 07/25/2014 07/25/2014 08/07/2014
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
NO GFCI MUCH RM
RSLV 07/25/2014 07/25/2014 08/07/2014
 
006 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
ALL - BATHROOM FIXTURE THROUGHOUT SUITABLE FOR DRY LOCATION ONLY. 410.10(A)
RSLV 08/07/2014 08/07/2014 08/26/2014
 
007 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
ALL - FIXTURE OVER TUB NOT DAMPER PROOF. 410.10(D)
RSLV 08/07/2014 08/07/2014 08/26/2014