Electrical Application Details for App #: B350176
Premises: 852 OCEAN AVENUE BROOKLYN BIN: 3118802     Block: 5162   Lot: 34
   
Application Completed and Certified

Filed: 854 OCEAN AV Census Tract:   514 Health Area:  7210
DORCHESTER STREET Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
DOB Cross Street(s):   CORTELYOU ROAD,    DORCHESTER ROAD
Status:   C - JOB IS SIGNED OFF 04/22/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/18/2012 11:53 AM
Application Entered:   05/18/2012 Job Start Date:   05/18/2012
Last Change:   04/22/2013 Job End Date:   02/17/2013
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     04/16/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEZIN COPANY
Owner Business Name: COPANY MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  125.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/22/2013 Notice: C - CALL TO OFFICE 01/18/2013
Power Issued: 04/22/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:   DEVICE NO. 3P2999

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B350176
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/13/2012 12/17/2012 JTE A (45) (5) Y
INSPECTION COMMENTS: N
 
(2) 01/14/2013 01/18/2013 CJH H X (50) (0) Y
INSPECTION COMMENTS: N
 
(3) 03/19/2013 03/25/2013 RHO J Y (30) (0) Y
INSPECTION COMMENTS: VIOLATION #005 IS STILL OPEN
 
(4) 04/16/2013 04/22/2013 CJH C R E (85) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B350176
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
1 1/4" METAL RACEWAY FROM LOAD SIDE OF DISCONNECT TO CONTROL CABINET
RSLV 12/13/2012 01/14/2013 03/19/2013
 
002 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
1" METAL RACEWAY FROM CONTROL CABINET FEEDING MOTOR
RSLV 12/13/2012 01/14/2013 03/19/2013
 
003 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
1 1/4" METAL RACEWAY FROM DISCONNECT FEEDING CONTROL
RSLV 12/13/2012 01/14/2013 03/19/2013
 
004 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
1" METAL RACEWAY FROM CONTROL CABINET FEEDING MOTOR G.E.C. NEEDSMIGB/CLAMP
RSLV 12/13/2012 01/14/2013 03/19/2013
 
005 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
ELEVATOT PIT GFCI DOES NOT RESET
RSLV 12/13/2012 03/19/2013 04/16/2013