Electrical Application Details for App #: B350093
Premises: 25 PIERREPONT STREET BROOKLYN BIN: 3001728     Block: 234   Lot: 1
   
Application Completed and Certified

Filed: 152 WILLOW ST Census Tract:   3.01 Health Area:  2300
BAS, 1FL.2 FL,3FL Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   CLARK STREET,    PIERREPONT STREET
Status:   C - JOB IS SIGNED OFF 06/09/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/17/2012 6:27 AM
Application Entered:   05/17/2012 Job Start Date:   05/18/2012
Last Change:   06/09/2014 Job End Date:   11/02/2012
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     06/03/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $69.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GIL BOOSIDIN
Owner Business Name: BH25PIERMONT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    13           
002    12  15    12  12             
003    11  12    11         
Buildings Total 28  40    24  28              
Total Units : 126 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/09/2014 Notice: 1 - FIRST NOTICE 05/19/2014
Power Issued: 06/09/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B350093
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/28/2013 04/01/2013 HRB V (60) (8) Y
INSPECTION COMMENTS: NEED TO CHECK ALL CIRCUITS
 
(2) 05/13/2014 05/19/2014 PAT A Y (60) (2) Y
INSPECTION COMMENTS: #4 AND 8 STILL REMAIN
 
(3) 06/03/2014 06/09/2014 CLC C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B350093
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NEED DIR
RSLV 03/28/2013 03/28/2013 05/13/2014
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
HOT TUB MOTOR AND OUTLETS IN KITCHEN
RSLV 03/28/2013 03/28/2013 05/13/2014
 
003 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
OUTLETS SET BACK TO FAR IN KITCHEN
RSLV 03/28/2013 03/28/2013 05/13/2014
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
NEED BUSHING ON ALL FEEDERS
RSLV 03/28/2013 05/13/2014 06/03/2014
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ALL OUTLETS MUST BE TAMPER PROOF
RSLV 03/28/2013 03/28/2013 05/13/2014
 
006 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
NEED SWITCHES FOR AC BLOWERS BLOWERS FEED FROM PANELS
RSLV 03/28/2013 03/28/2013 05/13/2014
 
007 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
LIGHT IN CLOSET AND IN SHOWERS
RSLV 03/28/2013 03/28/2013 05/13/2014
 
008 (999) OTHER
NEUTRAL BONDED AFTER MAIN SERVICE IN BOTH AC SWITCHES 250.92
RSLV 03/28/2013 05/13/2014 06/03/2014
 
009 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
ALL FLRS.- ENTIRE HOUSE AFCT. NOT SUFFICIENT
RSLV 05/13/2014 05/13/2014 06/03/2014
 
010 (999) OTHER
ALL PNL. 12/3 NEED HANDLE TIE 210.41(D)
RSLV 05/13/2014 05/13/2014 06/03/2014