| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER SERVICE NOT BONDED PLP METER IN TROUGH |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 002 |
(999) |
OTHER A NEUTRAL NOT BONDED IN PLP PANEL 250.28 |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE WATER GROUND CABLE STRING REMOVES FROM CABLE |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 004 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY WATER GROUND CABLE NOT PROPER INSTALL TO WATER PIPE CEILING |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 005 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE FEEDS TO APTS OVER FUSE |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 006 |
(999) |
OTHER B SUPP GROUND MISSING RACEWAY NOT CONTINOUS 250.53 D.2 |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 007 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) FIXTURE MISSING SWITCH |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 008 |
(999) |
OTHER C SPLICE BOX IN CEILING BACK ROOM 314.29 |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 009 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY NO PANEL DIR THROUGHOUT |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 010 |
(999) |
OTHER D NO C.T OUTLET IN KITCHEN SOME APT 210.11.C.1 |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 011 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS NO AC OUTLET IN APT SAME APT |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 012 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED NO ARC FAULT BROKEN |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 013 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX KO MISSING SERVICE APT PANEL |
RSLV |
11/28/2012 |
11/28/2012 |
11/28/2012 |
| |
| 014 |
(999) |
OTHER E SINGLE POLE BREAKERS MADE 2 POLE 240.15 B2 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 015 |
(999) |
OTHER F 12X3 SAME PHASE 300.20 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 016 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BOX CABLE NOT PROPERLY INSTALL IN CEILING |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 017 |
(999) |
OTHER G NO ACCESS TO SEE FOR OTHER TENANTS 240.24.B |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 018 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) EMT NOT PROPERLY INSTALL TO WATER PIPE |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 019 |
(999) |
OTHER H NO GROUNDING BON FOR UTILITY COMPANY 250.94 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 020 |
(999) |
OTHER I ALL SER SW NOT BONDED TOGETHER 250 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 021 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE DEF FICTURE IN USE IN APT BSMT |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 022 |
(999) |
OTHER J OUTLET NOT TAMPER PROOF THROUGHOUT 406.11 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 023 |
(999) |
OTHER K DOUBLE LUG IN PANEL THROUGHOUT 110.14 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 024 |
(999) |
OTHER L PANEL BONDED IN APT THROUGHOUT 250.24.A.5 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 025 |
(999) |
OTHER M 12X3 NEED 2 POLE BREAKERS THROUGHOUT 210.48 |
RSLV |
11/28/2012 |
11/28/2012 |
02/26/2013 |
| |
| 026 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED 4TH FLOOR OUTLETS NOT GROUNDED 250.146Q |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 027 |
(999) |
OTHER BATHROOM GFCI SHEET ROCK SCREWS USED AS GROUND 250.8 |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 028 |
(999) |
OTHER THROUGHOUT CIRCUITS NOT GROUPED 210.4D |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 029 |
(999) |
OTHER THROUGHOUT 2 POLE BREAKERS OR HANDLE LIE NEED FOR MULTILITYCONDUCTORS 210.4B |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 030 |
(999) |
OTHER THROUGHOUT 12X3 CONDUCTOR ON SAME PHASE 300.20 |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 031 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER 2ND KITCHEN COUNTER 210.52 |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 032 |
(999) |
OTHER COLLECTIVE BAR NOT PER ART 250.64 (F3) |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 033 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE FOR SERVICE 250.50 |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 034 |
( 53) |
GFCI HAS NOT BEEN PROVIDED THROUGHOUT WASH ROOM AREA GFCI PROVIDED 210.8 |
RSLV |
02/26/2013 |
03/15/2013 |
04/15/2013 |
| |
| 035 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED ALL OUTLETS |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 036 |
(999) |
OTHER CIRCUITS ARE NOT GROUPED IN PANELS (210.4D) |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 037 |
(999) |
OTHER 3 WIRE CIRCUITS NOT ON TWO POLE BREAKERS (210.4B) |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 038 |
(999) |
OTHER 12/3 CIRCUITS ARE ON SAME PHASE IN PANELS (300.20) |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 039 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER ON KITCHEN COUNTER TOP |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 040 |
( 53) |
GFCI HAS NOT BEEN PROVIDED WASH ROOM AREA NOT GFI PROTECTED AND ALL OUTLETS IN BSMT |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 041 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY NO GROUND OR BONDING IN PLP PANEL |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 042 |
(138) |
METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY RACEWAY NOT CONTINOUS FROM SERVICE SWITCHES TO WATER MAIN |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 043 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ALL OUTLETS SWITCHES NOT BONDED |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 044 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE ALL FEEDERS IN BSMT AND APT PANELS |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 045 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER NEED LIGHT GOING DOWNSTAIRS TO BSMT |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 046 |
(999) |
OTHER NEED TO FIRE STOP RACEWAY FROM BSMT GOING UPSTAIRS 300.21 |
RSLV |
04/15/2013 |
04/15/2013 |
06/07/2013 |
| |
| 047 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX KO MISSING IN PANEL ALL SIZES |
RSLV |
06/07/2013 |
06/07/2013 |
06/07/2013 |
| |
| 048 |
(999) |
OTHER WATER GROUND RACEWAY NOT CONTINOUS 250.64 |
RSLV |
06/07/2013 |
06/07/2013 |
06/07/2013 |
| |
| 049 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE SER SW NO MIGB INSTALLED |
RSLV |
06/07/2013 |
06/07/2013 |
06/07/2013 |
| |
| 050 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED MIGB MISSING 2ND BONDING SCREW |
RSLV |
06/07/2013 |
06/07/2013 |
06/07/2013 |
| |
| 051 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX KO MISSING IN PANEL ALL SIZES |
RSLV |
06/07/2013 |
06/07/2013 |
07/22/2013 |
| |
| 052 |
(999) |
OTHER WATER GROUND RACEWAY NOT CONTINOUS 250.64 |
RSLV |
06/07/2013 |
06/07/2013 |
07/22/2013 |
| |
| 053 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE SER SW NO MIGB INSTALLED |
RSLV |
06/07/2013 |
06/07/2013 |
07/22/2013 |
| |
| 054 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED MIGB MISSING 2ND BONDING SCREW |
RSLV |
06/07/2013 |
06/07/2013 |
07/22/2013 |