BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B348920
Premises: 756 MARCY AVENUE BROOKLYN BIN: 3050620     Block: 1803   Lot: 45
   
Application Completed and Certified

Filed: 756 MARCY AV Census Tract:   251 Health Area:  2000
1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   303
DOB Cross Street(s):   LEXINGTON AVENUE,    QUINCY STREET
Status:   C - JOB IS SIGNED OFF 08/22/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/13/2012 9:21 AM
Application Entered:   04/13/2012 Job Start Date:   04/13/2012
Last Change:   08/22/2013 Job End Date:   04/12/2013
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     07/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010985 Licensee Name: LINDEN J TUDOR
Firm: 002700 Firm Name: LINTECH ELECTRIC, INC
Firm Phone: 718-941-3766  Firm Address: 3006 TILDEN AVENUE BROOKLYN NY 11226 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $316.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MENDEL GOLD
Owner Business Name: 756 REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  6  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20    12  12             
002    20    12  12             
003  12    12  10             
004  12    12  10             
005    20    12  12             
Buildings Total 84    60  56                
Total Units : 205 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 6 - Removed Meters 6 = Total Meters 6

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/13/2012 Notice: 1 - FIRST NOTICE 06/14/2013
Power Issued: 04/13/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B348920
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/28/2012 12/05/2012 CCH V D (150) (13) Y
INSPECTION COMMENTS: WALK THROUGH APTS ONLY INSPECTED SERVICE
 
(2) 11/28/2012 12/05/2012 CCH V R D (150) (12) Y
INSPECTION COMMENTS: N
 
(3) 02/26/2013 03/05/2013 CJH A R E (100) (9) Y
INSPECTION COMMENTS: N
 
(4) 03/15/2013 03/19/2013 CJH H X E (30) (0) Y
INSPECTION COMMENTS: ACCESS ONLY 3L AND 1ST FK
 
(5) 04/15/2013 04/22/2013 HRB V R D (50) (12) Y
INSPECTION COMMENTS: NEED TO CHECK ALL APT OVER AGAIN
 
(6) 06/07/2013 06/07/2013 CCH A R E (70) (4) Y
INSPECTION COMMENTS: N
 
(7) 06/07/2013 06/14/2013 CCH A R E (70) (4) Y
INSPECTION COMMENTS: N
 
(8) 06/18/2013 06/25/2013 CJH N (50) (0) Y
INSPECTION COMMENTS: N
 
(9) 07/22/2013 07/29/2013 CCH C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B348920
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE NOT BONDED PLP METER IN TROUGH
RSLV 11/28/2012 11/28/2012 11/28/2012
 
002 (999) OTHER
A NEUTRAL NOT BONDED IN PLP PANEL 250.28
RSLV 11/28/2012 11/28/2012 11/28/2012
 
003 ( 19) DEFECTIVE WIRING IS IN USE
WATER GROUND CABLE STRING REMOVES FROM CABLE
RSLV 11/28/2012 11/28/2012 11/28/2012
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND CABLE NOT PROPER INSTALL TO WATER PIPE CEILING
RSLV 11/28/2012 11/28/2012 11/28/2012
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
FEEDS TO APTS OVER FUSE
RSLV 11/28/2012 11/28/2012 11/28/2012
 
006 (999) OTHER
B SUPP GROUND MISSING RACEWAY NOT CONTINOUS 250.53 D.2
RSLV 11/28/2012 11/28/2012 11/28/2012
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
FIXTURE MISSING SWITCH
RSLV 11/28/2012 11/28/2012 11/28/2012
 
008 (999) OTHER
C SPLICE BOX IN CEILING BACK ROOM 314.29
RSLV 11/28/2012 11/28/2012 11/28/2012
 
009 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PANEL DIR THROUGHOUT
RSLV 11/28/2012 11/28/2012 11/28/2012
 
010 (999) OTHER
D NO C.T OUTLET IN KITCHEN SOME APT 210.11.C.1
RSLV 11/28/2012 11/28/2012 11/28/2012
 
011 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
NO AC OUTLET IN APT SAME APT
RSLV 11/28/2012 11/28/2012 11/28/2012
 
012 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
NO ARC FAULT BROKEN
RSLV 11/28/2012 11/28/2012 11/28/2012
 
013 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
KO MISSING SERVICE APT PANEL
RSLV 11/28/2012 11/28/2012 11/28/2012
 
014 (999) OTHER
E SINGLE POLE BREAKERS MADE 2 POLE 240.15 B2
RSLV 11/28/2012 11/28/2012 02/26/2013
 
015 (999) OTHER
F 12X3 SAME PHASE 300.20
RSLV 11/28/2012 11/28/2012 02/26/2013
 
016 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BOX CABLE NOT PROPERLY INSTALL IN CEILING
RSLV 11/28/2012 11/28/2012 02/26/2013
 
017 (999) OTHER
G NO ACCESS TO SEE FOR OTHER TENANTS 240.24.B
RSLV 11/28/2012 11/28/2012 02/26/2013
 
018 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
EMT NOT PROPERLY INSTALL TO WATER PIPE
RSLV 11/28/2012 11/28/2012 02/26/2013
 
019 (999) OTHER
H NO GROUNDING BON FOR UTILITY COMPANY 250.94
RSLV 11/28/2012 11/28/2012 02/26/2013
 
020 (999) OTHER
I ALL SER SW NOT BONDED TOGETHER 250
RSLV 11/28/2012 11/28/2012 02/26/2013
 
021 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
DEF FICTURE IN USE IN APT BSMT
RSLV 11/28/2012 11/28/2012 02/26/2013
 
022 (999) OTHER
J OUTLET NOT TAMPER PROOF THROUGHOUT 406.11
RSLV 11/28/2012 11/28/2012 02/26/2013
 
023 (999) OTHER
K DOUBLE LUG IN PANEL THROUGHOUT 110.14
RSLV 11/28/2012 11/28/2012 02/26/2013
 
024 (999) OTHER
L PANEL BONDED IN APT THROUGHOUT 250.24.A.5
RSLV 11/28/2012 11/28/2012 02/26/2013
 
025 (999) OTHER
M 12X3 NEED 2 POLE BREAKERS THROUGHOUT 210.48
RSLV 11/28/2012 11/28/2012 02/26/2013
 
026 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
4TH FLOOR OUTLETS NOT GROUNDED 250.146Q
RSLV 02/26/2013 03/15/2013 04/15/2013
 
027 (999) OTHER
BATHROOM GFCI SHEET ROCK SCREWS USED AS GROUND 250.8
RSLV 02/26/2013 03/15/2013 04/15/2013
 
028 (999) OTHER
THROUGHOUT CIRCUITS NOT GROUPED 210.4D
RSLV 02/26/2013 03/15/2013 04/15/2013
 
029 (999) OTHER
THROUGHOUT 2 POLE BREAKERS OR HANDLE LIE NEED FOR MULTILITYCONDUCTORS 210.4B
RSLV 02/26/2013 03/15/2013 04/15/2013
 
030 (999) OTHER
THROUGHOUT 12X3 CONDUCTOR ON SAME PHASE 300.20
RSLV 02/26/2013 03/15/2013 04/15/2013
 
031 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
2ND KITCHEN COUNTER 210.52
RSLV 02/26/2013 03/15/2013 04/15/2013
 
032 (999) OTHER
COLLECTIVE BAR NOT PER ART 250.64 (F3)
RSLV 02/26/2013 03/15/2013 04/15/2013
 
033 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
FOR SERVICE 250.50
RSLV 02/26/2013 03/15/2013 04/15/2013
 
034 ( 53) GFCI HAS NOT BEEN PROVIDED
THROUGHOUT WASH ROOM AREA GFCI PROVIDED 210.8
RSLV 02/26/2013 03/15/2013 04/15/2013
 
035 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
ALL OUTLETS
RSLV 04/15/2013 04/15/2013 06/07/2013
 
036 (999) OTHER
CIRCUITS ARE NOT GROUPED IN PANELS (210.4D)
RSLV 04/15/2013 04/15/2013 06/07/2013
 
037 (999) OTHER
3 WIRE CIRCUITS NOT ON TWO POLE BREAKERS (210.4B)
RSLV 04/15/2013 04/15/2013 06/07/2013
 
038 (999) OTHER
12/3 CIRCUITS ARE ON SAME PHASE IN PANELS (300.20)
RSLV 04/15/2013 04/15/2013 06/07/2013
 
039 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
ON KITCHEN COUNTER TOP
RSLV 04/15/2013 04/15/2013 06/07/2013
 
040 ( 53) GFCI HAS NOT BEEN PROVIDED
WASH ROOM AREA NOT GFI PROTECTED AND ALL OUTLETS IN BSMT
RSLV 04/15/2013 04/15/2013 06/07/2013
 
041 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO GROUND OR BONDING IN PLP PANEL
RSLV 04/15/2013 04/15/2013 06/07/2013
 
042 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
RACEWAY NOT CONTINOUS FROM SERVICE SWITCHES TO WATER MAIN
RSLV 04/15/2013 04/15/2013 06/07/2013
 
043 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL OUTLETS SWITCHES NOT BONDED
RSLV 04/15/2013 04/15/2013 06/07/2013
 
044 ( 42) BUSHINGS ARE MISSING OR LOOSE
ALL FEEDERS IN BSMT AND APT PANELS
RSLV 04/15/2013 04/15/2013 06/07/2013
 
045 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
NEED LIGHT GOING DOWNSTAIRS TO BSMT
RSLV 04/15/2013 04/15/2013 06/07/2013
 
046 (999) OTHER
NEED TO FIRE STOP RACEWAY FROM BSMT GOING UPSTAIRS 300.21
RSLV 04/15/2013 04/15/2013 06/07/2013
 
047 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
KO MISSING IN PANEL ALL SIZES
RSLV 06/07/2013 06/07/2013 06/07/2013
 
048 (999) OTHER
WATER GROUND RACEWAY NOT CONTINOUS 250.64
RSLV 06/07/2013 06/07/2013 06/07/2013
 
049 ( 42) BUSHINGS ARE MISSING OR LOOSE
SER SW NO MIGB INSTALLED
RSLV 06/07/2013 06/07/2013 06/07/2013
 
050 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
MIGB MISSING 2ND BONDING SCREW
RSLV 06/07/2013 06/07/2013 06/07/2013
 
051 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
KO MISSING IN PANEL ALL SIZES
RSLV 06/07/2013 06/07/2013 07/22/2013
 
052 (999) OTHER
WATER GROUND RACEWAY NOT CONTINOUS 250.64
RSLV 06/07/2013 06/07/2013 07/22/2013
 
053 ( 42) BUSHINGS ARE MISSING OR LOOSE
SER SW NO MIGB INSTALLED
RSLV 06/07/2013 06/07/2013 07/22/2013
 
054 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
MIGB MISSING 2ND BONDING SCREW
RSLV 06/07/2013 06/07/2013 07/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back