BIS Menu  |  After Hours Variance Permits  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B347631
Premises: 471 FULTON STREET BROOKLYN BIN: 3000404     Block: 152   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 151 LAWRENCE ST Census Tract:   11 Health Area:  2300
3RD FLOOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   WILLOUGHBY STREET,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 02/17/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/29/2012 3:58 PM
Application Entered:   02/29/2012 Job Start Date:   02/29/2012
Last Change:   02/17/2017 Job End Date:   12/31/2012
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     02/13/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011747 Licensee Name: IGOR BRON
Firm: 003605 Firm Name: E ELEC'L CONTR'G LLC
Firm Phone: 718-336-0276  Firm Address: 2355 MCDONALD AVENUE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $300.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELI KRAIEM
Owner Business Name: FULTON REALTY VENTURE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    120  120  30  120             
Buildings Total 120  120  30  120                
Total Units : 391 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 25 + New Meters 1 - Removed Meters 0 = Total Meters 26

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/29/2012 Notice: 1 - FIRST NOTICE 10/27/2016
Power Issued: 02/29/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B347631
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/26/2016 10/27/2016 CJH V (70) (5)
INSPECTION COMMENTS: NOT FINAL, ELECTRICIAN NOT FAMILLIAR WITH JOB. SVC NOT INSPECTED
 
(2) 11/30/2016 12/01/2016 HRB J Y (80) (0)
INSPECTION COMMENTS: FAILED
 
(3) 02/13/2017 02/17/2017 DAH C R (45) (0)
INSPECTION COMMENTS: OK

OBJECTION FOR APPLICATION #: B347631
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (228) USING PANEL AS A RACEWAY
(FLOOR: 003) 003 FL REAR OF ROOM BL 318 312.8
RSLV 10/26/2016 10/26/2016 11/30/2016
 
002 (999) OTHER
(FLOOR: 003) 003 FL REAR OF ROOM BL 318 PNL CKT NOT GROUPED 210.4D
RSLV 10/26/2016 10/26/2016 02/13/2017
 
003 (999) OTHER
(FLOOR: 003)003 FL REAR OF ROOM BL 318 PNL MULTI CKT NEED TWO POLE BRAKERS210.4B
RSLV 10/26/2016 10/26/2016 11/30/2016
 
004 (999) OTHER
(FLOOR: 003)003 FL THROUGHOUT LUMINAIRES QUICK DISCONNECT MISSING 410.130
RSLV 10/26/2016 10/26/2016 11/30/2016
 
005 (999) OTHER
(FLOOR: 003) 003 FL THROUGHOUT LUMINAIRES NOT SUPPORT 410.36
RSLV 10/26/2016 10/26/2016 02/13/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Applications  |  Electrical Inspection Work Order  |  Back