BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B346524
Premises: 778 48 STREET BROOKLYN BIN: 3012768     Block: 777   Lot: 36
   
Application Completed and Certified

Filed: 4802 8 AV Census Tract:   108 Health Area:  6700
BASEMENT, 1FL Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
DOB Cross Street(s):    48 STREET,    49 STREET
Status:   C - JOB IS SIGNED OFF 03/19/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/20/2012 2:31 PM
Application Entered:   01/20/2012 Job Start Date:   01/26/2012
Last Change:   03/19/2013 Job End Date:   05/02/2012
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     03/13/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011983 Licensee Name: PETER Z LI
Firm: 003654 Firm Name: P.L. ELEC'L CONTR'G CORP
Firm Phone: 212-608-8868  Firm Address: 25 MONROE STREET.1ST FLOOR NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $295.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEPHANIE WU
Owner Business Name: WJS MANAGEMENT LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/20/2012 Notice: 1 - FIRST NOTICE 01/03/2013
Power Issued: 01/20/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B346524
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/26/2012 01/03/2013 DEX A E (30) (7) Y
INSPECTION COMMENTS: N
 
(2) 03/13/2013 03/19/2013 JTE C R E (15) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B346524
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT 200 AMP NEW SERVICE SWITCHES NO GROUND FROM WATER MAIN
RSLV 12/26/2012 12/26/2012 03/13/2013
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO DIRECTORY FOR ALL PANELS THROUGHOUT
RSLV 12/26/2012 12/26/2012 03/13/2013
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
200AMP SERVICE SWITCH MISSING NO SEAL
RSLV 12/26/2012 12/26/2012 03/13/2013
 
004 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
2 INCH CONDUIT FROM SERVICE SWITCH TO DRAFT NO SUPPORT
RSLV 12/26/2012 12/26/2012 03/13/2013
 
005 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
BUGS IN DRAFT APPROVED FOR 2 WIRES ONLY PER SPLICE
RSLV 12/26/2012 12/26/2012 03/13/2013
 
006 (142) SWITCHES IS LOCATED MORE THAN 6FT 7IN ABOVE FLOOR
DISCONNECT SWITCHES AND PANELS OVER 6' 7"
RSLV 12/26/2012 12/26/2012 03/13/2013
 
007 (229) SPLICE BOXES NOT ACCESSIBLE
SPLICE BOX FEEDING FEEDERS TO APARTMENT NOT ACCESSIBLE
RSLV 12/26/2012 12/26/2012 03/13/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back