BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B346258
Premises: 70 EAST 8 STREET BROOKLYN BIN: 3124073     Block: 5321   Lot: 51
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 70 E 8 ST Census Tract:   504 Health Area:  5310
5D Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11218 Community Board:   307
DOB Cross Street(s):   KERMIT PLACE,    KERMIT PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   02/10/2012 Job Start Date:   02/13/2012
Last Change:   08/22/2025 Job End Date:   01/31/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PETER GREENE       On     01/05/2012      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: 011203 Licensee Name: BECALEL STEINBERG
Firm: 001700 Firm Name: B & S ELEC'L CONTR CO INC
Firm Phone: 718-972-1089  Firm Address: 4317 15TH AVENUE BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $70.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MR FRIED
Owner Business Name: B T REALTY LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice:  01/11/2012
Power Issued: Response: F - FILED TO REMOVE OBJECTION 02/10/2012

Follow-Up: F - FILED TO REMOVE OBJECTION 02/10/2012
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B346258
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/05/2012 01/11/2012 PGR W (5) (5)
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B346258
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO ELECT PERMIT FOR PANEL
OPEN 01/05/2012 01/05/2012
 
002 (999) OTHER
ALL FEEDER CONDUCTOR FROM OLD FUSE BOX TO PANEL MOT IN SAMERACEWAY 300.3B
OPEN 01/05/2012 01/05/2012
 
003 (999) OTHER
ALL BRANCH CIRCUITS FROM OLD FUSE BOX TO PANEL NOT IN SAME RACEWAY300.3B
OPEN 01/05/2012 01/05/2012
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL
OPEN 01/05/2012 01/05/2012
 
005 ( 19) DEFECTIVE WIRING IS IN USE
NEUTRAL FOR CIRCUIT NOT CONNECTED PANEL
OPEN 01/05/2012 01/05/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.