BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B346219
Premises: 97 WAVERLY AVENUE BROOKLYN BIN: 3394430     Block: 1889   Lot: 23
   
Application Completed and Certified

Filed: 97 WAVERLY AV Census Tract:   191 Health Area:  1410
BSMT,1ST, 2ND & 3RD FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11205 Community Board:   302
Related Job Number:    301792512
DOB Cross Street(s):   PARK AVENUE,    MYRTLE AVENUE
Status:   C - JOB IS SIGNED OFF 08/02/2013 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/10/2012 9:28 AM
Application Entered:   01/10/2012 Job Start Date:   01/10/2012
Last Change:   08/02/2013 Job End Date:   09/30/2012
Appointment Status:   
Last Inspection By:   BANYA, E       On     07/24/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012072 Licensee Name: CLINTON COURTNEY
Firm: 003770 Firm Name: TRINCITY ELECTRIC, INC
Firm Phone: 718-712-4300  Firm Address: 224-17 MERRICK BLVD SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $503.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   WALK-UP APARTMENT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NADAV HAMO
Owner Business Name: ILE CONSTRUCTION, INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1 400 AMP SERVICE SWITCH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1 SET 500 MCM WIRE
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  8 20-1 PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BSMT  12  12    12             
001  1FL  50  60    40  50         
002  2FL  50  60    40  50         
003  3FL  50  60    40  50         
Buildings Total 162  192    125  162     21           
Total Units : 662 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/10/2012 Notice: 1 - FIRST NOTICE 04/30/2013
Power Issued: 01/10/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B346219
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/25/2013 04/30/2013 CJH A E (60) (4) Y
INSPECTION COMMENTS: DISHWASHER NOT INSTALLED
 
(2) 05/20/2013 05/23/2013 CJE N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR CAN NOT REACH OWNER FOR ACCESS
 
(3) 07/24/2013 07/30/2013 EBA C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B346219
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR LAUNDRY RECEPTACLES OUTLETS NOT PROVIDED 210.52(3F)
RSLV 04/25/2013 04/25/2013 07/24/2013
 
002 (999) OTHER
GROUNDING CONDUCTORS NOT CONTINUOUS 250.64(3)(E)
RSLV 04/25/2013 04/25/2013 07/24/2013
 
003 (999) OTHER
95 ENTRANCE 3RD FL, MIDDLE APT PENINSULAR RECEPTACLE OUTLET. NOTGFCI PROTECTED 210.8
RSLV 04/25/2013 04/25/2013 07/24/2013
 
004 (220) DOUBLE LUGGING IN SERVICE SWITCH
CELLAR DOUBLE LUGGING O WATER MAIN GOUND LUG 110.16A
RSLV 04/25/2013 04/25/2013 07/24/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back