BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B345465
Premises: 388 BRIDGE STREET BROOKLYN BIN: 3397720     Block: 152   Lot: 37
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 388 BRIDGE ST Census Tract:   11 Health Area:  2300
C, 1-52, ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    302376747
DOB Cross Street(s):   WILLOUGHBY STREET,    FULTON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/16/2011 4:52 PM
Application Entered:   12/16/2011 Job Start Date:   12/26/2011
Last Change:   08/22/2025 Job End Date:   12/31/2013
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     10/18/2021      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010501 Licensee Name: RUSS FLAUM
Firm: 000526 Firm Name: FIVE STAR ELECTRIC CORP.
Firm Phone: 718-641-5000  Firm Address: 101-32 101ST STREET OZONE PARK NY 11416 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011027 SEGAL, GARY 000526 FIVE STAR ELECTRIC CORP.
010682 SQUILLARI, RICHARD 000526 FIVE STAR ELECTRIC CORP.
011004 DILLON, JOHN J 000526 FIVE STAR ELECTRIC CORP.

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: GREGG WOLPERT
Owner Business Name: 388 BRIDGE ST LLC
Authorized Representative:  GREGG WOLPERT
Relationship To Owner:   PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100A
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  1-800, 2-1200
E. Over 1200 AMPS  7  3-1600,4-4000
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  251  109-#4,49-#3,93-#2
B. Over #2 to 1/0  108  60-#1, 48-1/0
C. Over 1/0 to 250 MCM  38  18-2/0,20-3/0
D. Over 250 MCM  106  39-500, 67-600
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  351  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  19  5-100, 14-200
D. 3 Phase Over 225 AMPS  17  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    22  43  18  14  88  36  829  17  1500 
001    25  16  11  11  97  14  77  15  41     
002    14  23  56  48  43     
003    15  26  59  10  55  11     
004    16  29  63  37     
005    15  28  61  29  159  66     
006    15  27  60  25  104         
007    29  141  41  41  111             
008    29  141  41  41  111             
009    29  141  41  41  111             
010    29  141  41  41  111             
011    29  141  41  41  111             
012    29  141  41  41  111             
013    29  141  41  41  111             
014    28  126  47  38  108  41      75 
015    28  142  40  41  112             
016    28  142  40  41  112             
017    28  142  40  41  112             
018    28  142  40  41  112             
019    28  142  40  41  112             
020    28  142  40  41  112             
021    28  142  40  41  112             
022    28  142  40  41  112             
023    28  142  40  41  112             
024    28  142  40  41  112             
025    28  142  40  41  112             
026    26  126  45  36  101             
027    26  126  45  36  101             
028    26  126  45  36  101             
029    26  126  45  36  101             
030    28  126  47  38  108  24      113 
031    26  128  46  37  103             
032    26  128  46  37  103             
033    26  128  46  37  103             
034    26  128  46  37  103             
035    26  128  46  37  103             
036    26  128  46  37  103             
037    26  128  46  37  103             
038    26  128  46  37  103             
039    26  128  46  37  103             
040    26  128  46  37  103             
041    26  128  46  37  103             
042    26  128  46  37  103             
043    26  128  46  37  103             
044    23  112  41  32  91             
045    17  71  26  22  67  10  75 
046    18  84  31  31  71             
047    13  64  22  21  52             
048    18  84  31  31  71             
049    33  16  17  26             
050    18  82  28  29  69             
051    36  18  19  28             
052    41  19  21  31             
ROF    26  42  385  14  57  75 
Buildings Total 1267  5776  1898  1730  4984     1739     273     1838 
Total Units : 19505 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 352 #4-Wire 0 #10-Wire 5
Existing Meters 0 + New Meters 357 - Removed Meters 0 = Total Meters 357

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/16/2011 Notice: 1 - FIRST NOTICE 10/18/2021
Power Issued: 12/16/2011 Response:  

Follow-Up:
Contractor's Comments:  JOB #9738 WORK BEING FILED UNDER 2007 ELECTRICAL CODE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B345465
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2021 10/18/2021 EDB V (405) (10)
INSPECTION COMMENTS: SEE ATTACHMENT. INSPECT SERVICE ROOM, ROOF F/P AND GENERATOR ONLY. INSPECTION INCOMPLETE.

OBJECTION FOR APPLICATION #: B345465
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(FLOOR: 005)250.30,50,52 ROOF: GEN. 277/480 V NOT PROPERLY GND/BONDED ( MAINSERVICE 120/208 V)
OPEN 10/18/2021 10/18/2021
 
002 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
(ALL FLOORS) 215.5 NO FEEDER DIAGRAM FOR EMERGENCY POWER
OPEN 10/18/2021 10/18/2021
 
003 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(CELLAR) 110.26 NO WORKING SPACE ON TOP OF S. SW.
OPEN 10/18/2021 10/18/2021
 
004 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(CELLAR) 240.21, 695.1 UNDERSIZED TAP CONDUCTORS FOR JOCKEY PUMP
OPEN 10/18/2021 10/18/2021
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR) 250.30 1500 KVA T-FMR NOT PROPERLY GND/BONDED
OPEN 10/18/2021 10/18/2021
 
006 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM. 110.2 , AM. 408.60(A) INSTALLATION NOT PER CONTRACTORSDRAWING
OPEN 10/18/2021 10/18/2021
 
007 (255) NO FUSE COORDINATION EXISTS
(CELLAR)240.12 NO FUSE COORDINATION BETWEEN 1ST AND 2ND LEVEL
OPEN 10/18/2021 10/18/2021
 
008 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR)AM. 110.2 NO APPROVED DRAWING FOR OVER 1000 KVA ELECTRICSERVICE ROOM
OPEN 10/18/2021 10/18/2021
 
009 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) 250.50,52 NO ACCESS TO GND ROD CONNECTION
OPEN 10/18/2021 10/18/2021
 
010 (999) OTHER
(CELLAR)ADMINISTRATIVE PAA REQUIRED FOR QUANTITY OF S. SW(S) (TOTAL 16)
OPEN 10/18/2021 10/18/2021



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.