Electrical Application Details for App #: B344748
Premises: 630 48 STREET BROOKLYN BIN: 3012707     Block: 776   Lot: 18
   
Application Completed and Certified

Filed: 630 48 ST Census Tract:   98 Health Area:  6500
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
DOB Cross Street(s):    6 AVENUE,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 10/18/2013
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/25/2011 Job Start Date:   11/14/2011
Last Change:   10/18/2013 Job End Date:   03/30/2012
Appointment Status:   
Last Inspection By:   BANYA, E       On     06/26/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010606 Licensee Name: MYRON COHEN
Firm: 003435 Firm Name: A.T. ELEC'L CONTR'G, INC
Firm Phone: 718-234-9250  Firm Address: 1561 64TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $140.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: QI-DE LIU
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    20         
Buildings Total 20              
Total Units : 42 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/25/2011 Notice: 1 - FIRST NOTICE 10/22/2012
Power Issued: 11/25/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B344748
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/20/2012 06/27/2012 RJO N (15) (0) Y
INSPECTION COMMENTS: OWNER NO SHOW
 
(2) 10/16/2012 10/22/2012 JTE A E (40) (7) Y
INSPECTION COMMENTS: THIS APPLICATION ONLY FOR THE BASEMENT - 1ST AND 2ND FLOOR REFER TO B343205
 
(3) 01/23/2013 01/29/2013 HRB J Y E (30) (0) Y
INSPECTION COMMENTS: N
 
(4) 04/04/2013 04/08/2013 RJO N (20) (0) Y
INSPECTION COMMENTS: N
 
(5) 06/04/2013 06/11/2013 RJO N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(6) 06/26/2013 07/03/2013 EBA C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B344748
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (135) DEFECTIVE GROUND ROD IS IN USE
GROUND ROD VISIBLE/CANNOT DETERMINE IF ROD IS IN
RSLV 10/16/2012 10/16/2012 01/23/2013
 
002 (100) METERING FOR COMMON AREAS HAS NOT BEEN PROVIDED/ILLEGAL METERING
OUTSIDE BOILER ROOM LIGHTS/OUTLETS NOT ON PLP PANEL
RSLV 10/16/2012 01/23/2013 06/26/2013
 
003 (100) METERING FOR COMMON AREAS HAS NOT BEEN PROVIDED/ILLEGAL METERING
BASEMENT - HALLWAY LIGHTS BY ELECTRICAL CLOSET NOT ON PLP PANEL
RSLV 10/16/2012 01/23/2013 06/26/2013
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
BASEMENT - ALL PANELS IN BASEMENT ART 480.4
RSLV 10/16/2012 01/23/2013 06/26/2013
 
005 (184) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
OUTSIDE NO MAIN DISCONNECT SWITCHES ARE PROVIDED FOR BOILER ROOM ATREARSWITCHES BY HALLWAY ONLY GIVE ACCESS TO BASEMENT TENANTS
RSLV 10/16/2012 01/23/2013 06/26/2013
 
006 (184) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(ONTINUED FROM LAS LINE) NOT 1ST AND 2ND FLOOR TENANTS ART 620.51(A)
RSLV 10/16/2012 01/23/2013 06/26/2013
 
007 (999) OTHER
BASEMENT SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDINGAMEND 230.43
RSLV 10/16/2012 01/23/2013 06/26/2013