Electrical Application Details for App #: B344670
Premises: 28 JEFFERSON AVENUE BROOKLYN BIN: 3057383     Block: 1997   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 34 JEFFERSON AV Census Tract:   227 Health Area:  1300
WHOLE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   303
DOB Cross Street(s):   CLAVER PLACE,    FRANKLIN AVENUE
Status:   C - JOB IS SIGNED OFF 03/03/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/22/2011 12:24 PM
Application Entered:   11/22/2011 Job Start Date:   11/22/2011
Last Change:   03/03/2017 Job End Date:   11/22/2012
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     03/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011396 Licensee Name: SPIRO VALENTIS
Firm: 002831 Firm Name: VALENTIS ELECTRIC, INC.
Firm Phone: 718-726-0072  Firm Address: 32-21 58TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $2,771.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PETER STEPHANOPOULOS
Owner Business Name: BUILDERS R US
Authorized Representative:  PETER STEPHANOPOULOS
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  600 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  61  #6 THHN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 THHHN
D. Over 250 MCM  3  350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  61  20 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CIRCUITS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  SUPER  25  25  15               
001  1A-1M  40  70  20  30               
002  2A-2M  40  70  20  30               
003  3A-3M  40  70  20  30               
004  4A-M  40  70  20  30               
005  5A-5M  40  70  20  30               
006  6A-6M  40  70  20  30               
Buildings Total 265  445  123  195                  
Total Units : 1028 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 61 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/22/2011 Notice: 1 - FIRST NOTICE 01/12/2017
Power Issued: 11/22/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING FOR 61 APARTMENTS NEW SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B344670
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2016 10/18/2016 CJH V (108) (5)
INSPECTION COMMENTS: INSPECTED SVC SWITCHES, APT 5L,5H,3E, 3H, 3F
 
(2) 12/28/2016 12/28/2016 DIT N (39) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 01/11/2017 01/12/2017 CJH V Y (72) (2)
INSPECTION COMMENTS: INSPECTED APT 6L, B, C,E. 5 F,B,D,L 4 D,B,E,L 2 B,D,F,L
 
(4) 03/03/2017 03/03/2017 CLC C R (40) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: B344670
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 005) 005 5L KITCHEN COUNTER TOP GFCI 110.2
RSLV 10/18/2016 10/18/2016 03/03/2017
 
002 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(FLOOR: 005) 005 5L BATH ROOM LUMINAIRE NOT SUITABLE 410.10
RSLV 10/18/2016 10/18/2016 03/03/2017
 
003 (999) OTHER
(FLOOR: 005) 005 5H LEFT SIDE REAR BEDROOM NOT AFCI 210.12
RSLV 10/18/2016 10/18/2016 03/03/2017
 
004 (999) OTHER
(CELLAR) CELLAR SVC SW DISSIMILAR FUSES 110.2
RSLV 10/18/2016 10/18/2016 01/11/2017
 
005 (999) OTHER
(CELLAR) CELLAR SVC SWITCHES NOT PLAQUES PROVIDED 230.2
RSLV 10/18/2016 10/18/2016 03/03/2017
 
006 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(FLOOR: 006) 006 APT 6L BEDROOM LUMINAIRE NOT INSTALL 210.2
RSLV 01/11/2017 01/11/2017 03/03/2017
 
007 (999) OTHER
(FLOOR: 006)006 APT 6C KITCHEN COUNTER TOP GFCI SHARE WITH STOVE HOOD 210.52 B2
RSLV 01/11/2017 01/11/2017 03/03/2017