BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B344091
Premises: 161 BROADWAY BROOKLYN BIN: 3063558     Block: 2457   Lot: 28
   
Application Completed and Certified

Filed: 175 BROADWAY Census Tract:   549 Health Area:  0500
2000 AMP. SERVICE ONLY IN BSMT Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11211 Community Board:   301
DOB Cross Street(s):   BEDFORD AVENUE,    DRIGGS AVENUE
Status:   C - JOB IS SIGNED OFF 12/31/2013 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/02/2011 1:04 PM
Application Entered:   11/02/2011 Job Start Date:   11/02/2011
Last Change:   12/31/2013 Job End Date:   02/02/2012
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     12/21/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010765 Licensee Name: CESAR QUERY
Firm: 002004 Firm Name: C.Q. ELECTR'L CONTRG CORP
Firm Phone: 718-204-9255  Firm Address: 723 EAST 135TH STREET BRONX NY 10454 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $2,683.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CATERING & PARTY.
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JUAN FIGUEROA
Owner Business Name: 175 BROADWAY HOSP, LLC
Authorized Representative:  MIGUEL TRILLOS
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMP. ELEVATOR
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  800 AMP
E. Over 1200 AMPS  1  2000 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#6 ELEVATOR
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  16  3#4/0
D. Over 250 MCM  6  4#600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  14  200 AMP
D. 3 Phase Over 225 AMPS  2  400 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/02/2011 Notice: 1 - FIRST NOTICE 12/12/2013
Power Issued: 11/02/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  DOB-2K11-083 REPLACING B343842 DUE TO WRONG ADDRESS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B344091
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/10/2013 12/12/2013 JSB V E (150) (4) Y
INSPECTION COMMENTS: N
 
(2) 12/21/2013 12/23/2013 CLC C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B344091
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FP FEEDER IN NOT PROTECTED 695.6 (B) (1)
RSLV 12/10/2013 12/10/2013 12/21/2013
 
002 (999) OTHER
TROUGH FLANGES NOT PROPERLY INSTALLED 110.2B 376.23A
RSLV 12/10/2013 12/10/2013 12/21/2013
 
003 (999) OTHER
DIST PNL SECTIONS LOADSIDE 2000 AMP SVC SW FUSES NOT PROPERLYCOORDINATED 240.21
RSLV 12/10/2013 12/10/2013 12/21/2013
 
004 (999) OTHER
BSMT FA FEEDER RACEWAY NOT BONDED 250.92
RSLV 12/10/2013 12/10/2013 12/21/2013