| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
4 |
30 AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
100 A MAIN LUG |
| C. 3 Phase Up to 225 AMPS |
1 |
200 A MAIN LUG |
| D. 3 Phase Over 225 AMPS |
1 |
400 A MAIN BREAKER |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
30 AMP 3-PHASE |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY GROUND FOR ELECTRIC SYSTEM NOT CONNECTED TO WATER MAIN PROPERLY |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |
| |
| 002 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED 1ST FLOOR EXPOSED WIRES FOR HALLWAY FOR EXIT SIGN |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |
| |
| 003 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER 1ST FLOOR HALLWAY AND CHAINED HUNG FIXTURE NOT GROUNDED |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |
| |
| 004 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED 2ND FLOOR A/C UNITS GROUNDS IN PANELS ON NEUTRAL BARS |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |
| |
| 005 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED THROUGHOUT - GROUNDS NOT LABELED IN PANELS AND DISCONNECTS |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |
| |
| 006 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY THROUGHOUT NO DIRECTORY FOR PANELS THROUGHOUT |
RSLV |
05/21/2012 |
05/21/2012 |
07/31/2012 |